T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

32

Fig. 74. Program - Setpoint Offset (MOD 2 only).

Fig. 75. Reset Curve with Offset for MOD 2.

3.3. Second Modulating Output and
Relays

For the second Modulating Output and the two Relays (if
they are configured for Reset), the Offset parameter
displays on the Program menu as shown in Fig. 74.

3.3.1. SETPOINT OFFSET

(MOD 2 only)

This value is the number of degrees plus (+) or minus (-)
that you want the temperature to be offset from the
MOD 1 setpoint. See Fig. 75. For example, If you want
the MOD 2 setpoint to be 10°F less than the MOD 1
setpoint, enter -10°F.

1. From the menu, use the S and T buttons to

highlight OFFSET.

2. Press the X button to display the value.
3. Use the S and T buttons to increase/decrease the

desired temperature.

OFFSET Default: 0°F
OFFSET Range: -150°F to 150°F (-101°C to 66°C)

4. Press the X button to accept the value and display

the next option.

3.3.2. Second Modulating Output and
Relays Programming

To complete the programming of MOD 2 or a Relay,
perform the procedures in “3.2.5. THROTTLING RANGE
or DIFFERENTIAL” through “3.2.7. SETBACK OFFSET
(if configured)” beginning on page 30.

3.4. Exit Programming with Reset

When you finish programming the Modulating outputs and
the Relays, press the HOME button to leave programming
mode and return to the home screen.

This completes the programming procedure for
controllers that use Reset.

PROGRAM

MOD 2

MENU

PROGRAM

MOD 2

OFFSET

-10

F

o

ENTER

SETPOINT

OFFSET

FOR

MOD 2

M24547

MENU

PROGRAM

MOD 2

OFFSET

THROT RNG

ACTION

SETBACK

EXIT

SENSOR B

SP MAX A1

(BOILER MAX)

SP MIN A2

(BOILER MIN)

200

140

10

MOD 2

SETPOINT

OFFSET

-10°F

190

20

30

40

50

60

70

°F

80

150

160

170

210

220

180

°F

RESET B1

(OUTSD MIN)

RESET B2

(OUTSD MAX)

S

E

N

S

O

R

A

M24569

MOD 1

SETPOINT