Summary menu, Troubleshooting, Specifications – Honeywell T775U User Manual

Page 37: Power loss, Errors and diagnostics, Error message, Diagnostic messages

Advertising
background image

T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

37

62-0255—07

SUMMARY MENU

The Summary menu provides the ability to view the
schedule (E1 and E2 times) for each relay for each day of
the week.

NOTE: Scheduling must be enabled for the Summary

menu to display. Enabling the schedule is
determined in the Setup process for the Output
Options (see page 21).

Fig. 85. Summary Example - Monday Settings.

For each relay, the Summary display indicates the time
and temperature (in parenthesis) for each of the two
scheduled events E1 and E2.

1. Press the MENU button to view the menu.
2. Use the S and T buttons to highlight SUMMARY.
3. Press the X button to display the Summary

settings.

4. Use the X button to scroll forward through each day

of the week (Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, and Sunday).

5. While viewing a specific day, use the S and T

buttons to cycle through the individual relay
schedules for that day.

When finished, press the HOME button to return to the
home display screen.

If programmed for Reset control, the Summary setpoints
display as “RES” instead of a temperature value. For
example, the display would show:

MONDAY
STAGES
E1: 06:00AM (RES)

- indicating Reset

E2: 06:00PM (05)

- setback/offset degrees

TROUBLESHOOTING

Power Loss

The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.

Errors and Diagnostics

The controller provides an error message and diagnostic
status as described below.

Error Message

There is a two-character error code that displays in
response to controller software problems:

EE

EEPROM Failure— The values read back from
the EEPROM are not the same as written into the
EEPROM. This error cannot be field repaired. Replace
the device.

Diagnostic Messages

There are two diagnostic messages that can display in
response to sensor problems. The diagnostic codes that
can flash on the display are:

– –

Sensor Open or Shorted — Two dashes display

when a sensor (typically temperature) is open or
shorted. An open circuit is considered anything
greater than 1570 ohms (greater than 300F), shorted
anything less than 770 ohms (less than -73F). Which-
ever stages are operating with this sensor cease to
control (meaning relays go to OFF and proportional
outputs go to zero percent).

This message can also mean that the sensor is pro-
grammed, but not physically connected.

-60°F or 270°F (-51°C or 132°C) Blinking

Temperature Out of Range — The temperature

display blinks when the sensed temperature range is
outside of the display range, below -60°F (-51°C) or
above 270°F (132°C). The displayed value remains at
that displayed limit and control continues. Controller
continues to function unless an open or shorted state
is detected.

Blinking relay status

Relay Minimum Off Time is Active — On the home

screen, each relay’s indicator („) blinks while the
relay’s minimum off time is active.

SPECIFICATIONS

Power: 24, 120, or 240 Vac; 50/60 Hz

A separate earth ground is required for any power

source.

Power Consumption:
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz

Operating & Storage Temperature Ambient Rating:
• -40°F to 125°F (-40°C to 52°C) @ 50 Hz
• -40°F to 140°F (-40°C to 60°C) @ 60 Hz

Relative Humidity: 5% to 95% non-condensing

Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)

Modulating Outputs:
• 0-10 Vdc; drive a minimum of 2,000 Ohms
• 2-10 Vdc; drive a minimum of 2,000 Ohms
• 4-20 mA; drive a maximum of 600 Ohms
• Electronic Series 90
• Floating

MENU

SUMMARY

MENU

SUMMARY

MONDAY

RELAY 1-2

E1: 06:00AM (72)

E2: 06:00PM (65)

M24629