T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

6

Fig. 5. Sensor Wiring — 3-wire shielded cable

connection from Sensor A to 0-10 Vdc sensor

(H76xx humidity sensor shown).

Fig. 6. Sensor Wiring — 2-wire shielded cable

connection from 4-20 mA sensor to

T775 controller (loop powered wiring).

Fig. 7. Sensor Wiring — 2-wire shielded cable

connection from Sensor A to a 0-10 Vdc sensor

using separate transformer.

Fig. 8. Sensor Wiring — 2-wire 4-20mA sensor input

to T775 controller using a separate (Vdc only)

transformer.

M24550

THE T775U WILL ONLY ACCEPT 0-10 VDC AND 4-20 MA SENSORS.

IF REPLACING AN H775 CONTROLLER THAT USES A C7600B OR OTHER

2-10 VDC SENSOR, THE SENSOR MUST BE REPLACED. REPLACE THE

C7600B2008 SENSOR (2-10VDC OUTPUT) WITH THE H7655A1001

(0-10 VDC OUTPUT) SENSOR. THE H7655A1001 SENSOR USES THE SAME

ENCLOSURE STYLING AND WIRING AS THE C7600B.

1

NOTES:

1. SHIELDED CABLE MUST BE

CONNECTED TO A SEPARATE

EARTH GROUND. HOWEVER,

DO NOT GROUND SHIELDED

CABLE AT SENSOR END.

2. TO MINIMIZE NOISE PICKUP,

MAKE SENSOR CONNECTION

FROM SHIELDED CABLE AS

CLOSE AS POSSIBLE TO

SENSOR BODY.

EXAMPLE OF

H76XX HUMIDITY

SENSOR;

0-10 VDC

CONNECTION

SENSOR A

1

SENSOR B

C

S

V

T

T

VO

GND

VIN

C

S

V

SHIELDED CABLE

M24890C

V

S

SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND.

DO NOT GROUND SHIELDED CABLE AT SENSOR END.

TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED

CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.

THE T775 HAS AN INTEGRAL LOAD OF 500 OHMS WHICH RESULTS IN A

10V DROP AT 20MA. TO USE 4-20MA LOOP POWERED WIRING, THE SENSOR

MUST BE CAPABLE OF OPERATION WITH 8V OR LESS ACROSS ITS TERMINAL.

SENSOR A

SENSOR B

T

T

SHIELDED CABLE

PWR

OUT

COM

C

S

V

1

2

3

1

2

3

M24551

S

C

NOTES:

1. SHIELDED CABLE MUST BE

CONNECTED TO A SEPARATE

EARTH GROUND. HOWEVER,

DO NOT GROUND SHIELDED

CABLE AT SENSOR END.

2. TO MINIMIZE NOISE PICKUP,

MAKE SENSOR CONNECTION

FROM SHIELDED CABLE AS

CLOSE AS POSSIBLE TO

SENSOR BODY.

EXAMPLE OF

P7640A

PRESSURE

SENSOR;

0-10 VDC

CONNECTION

SENSOR A

SENSOR B

T

T

SHIELDED CABLE

PWR

OUT

COM

C

S

V

L1

(HOT)

L2

24 VAC

M24889A

S

C

NOTES:

1. SHIELDED CABLE MUST BE

CONNECTED TO A SEPARATE

EARTH GROUND. HOWEVER,

DO NOT GROUND SHIELDED

CABLE AT SENSOR END.

2. TO MINIMIZE NOISE PICKUP,

MAKE SENSOR CONNECTION

FROM SHIELDED CABLE AS

CLOSE AS POSSIBLE TO

SENSOR BODY.

EXAMPLE OF P7640A 4-20 MA SENSOR CONNECTION

SENSOR A

SENSOR B

T

T

SHIELDED CABLE

C

S

V

PWR

ZERO

COM

OUT

+

12-30 VDC

POWER SUPPLY