T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

8

Controller Wiring Details

The wiring connection terminals are shown in Fig. 11 and
are described in Table 2. See Fig. 12 – Fig. 18 beginning
on page 9 for typical T775U wiring applications.

Fig. 11. T775U Terminal and Feature Locations.

Table 2. Description of Wiring Terminal Connections.

Connection

Terminal

Label

Description

Connection

Terminal Label

Description

Sensors

Outputs

Sensor A

a

a

For applications that do not use Reset, only Sensor A is available for use.

C – common
S – signal
V – voltage

0-10 Vdc input: Universal
sensor for humidity, pressure,
temperature, etc.

Mod 1

+ - (Vdc or mA)
W R B (Series 90)

b

b

For Series 90 connections, you must insert a 340 Ohm resistor across terminals R and W. See Fig. 17 on page 10.
The resistor is included with the controller.

Modulating Output

Mod 2

S and V

4-20mA input; see Fig. 7 on
page 6

24 Vac Power

T T

Temperature Sensor; polarity
insensitive

24V +

+

24 Vac Hot

Common

-

24 Vac Common

Sensor B

T T

Temperature Sensor; polarity
insensitive

Ground

Earth Ground

c

c

A separate earth ground is required for all installations regardless of the power source (24, 120, or 240 Vac).

120 or 240 Vac Power

Input

120 Vac

120

120 Vac Power

DI

+ -

Digital Input (dry contact)

Common

COM

Common

Outputs

240 Vac

240

240 Vac Power

Relay 1

NO / COM /
NC

120-240 Vac Relay Output

Relay 2

C

NO

NC

C

NO

NC

T

T

B

R

W

+

+

B

R

W

+

SENSOR A

SENSOR B

MOD 2

MOD 1

KNOCKOUT A

DIGITAL

INPUT

POWER

120/240 VAC

OUTPUT

RELAY 2

KNOCKOUT D

POWER

24 VAC

OUTPUT

RELAY 1

KNOCKOUT C

KNOCKOUT E

WHEN USED FOR TEMPERATURE OR 4-20mA SENSING, SENSORS A

AND B USE THE TWO TT CONNECTIONS AND ARE POLARITY

INSENSITIVE.

FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT,

USE SIGNAL (+) & COMMON (-).

FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.

A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER

SOURCE (24, 120, OR 240 VAC)

1

2

1

2

M24553A

KNOCKOUT B

3

3

C

S

V

T

T

+

C

+

120

COM

240