272630D POSITION FEEDBACK AND AUXILIARY SWITCH ACCESSORY

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422

Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com

® U.S. Registered Trademark
© 2010 Honeywell International Inc.
95C-10941—02 T.D. Rev. 08-10
Printed in U.S.A.

Fig. 1. Installation of auxiliary board.

OPERATION

The first time the valve is powered, the microprocessor
will automatically cycle the valve through a full stroke to
calibrate its position. Any stroke between 1/2" (13 mm)
and 1" (25 mm) will be divided into 30 equal steps. Run
time will be proportional to stroke length. (For example:
nominal timing for 3/4" stroke is 63 seconds. For 1/2"
stroke this would be 42 seconds). The LED lights up
when terminals T5-T6 are powered, and flash when the
actuator is in motion.

NOTE: 272630D requires that the actuator be continu-

ously powered, so ML6984 must be wired in "5-
wire" configuration.

Fig. 2. Wiring and operation of auxiliary board

272630D.

The 272630D provides:

1. A 2-10 Vdc voltage proportional to the valve stem

position. This output is capable of sourcing up to
20 mA dc drive current.

2. An isolated "Form C" relay contact closure that

energizes when the valve is open more than the
setting of the trimmer potentiometer ("trim pot").

Position feedback voltage mirrors the control signal. For
ML6984 and direct acting ML7984 operation, see Fig. 3.
For reverse acting ML7984, see Fig. 4.

Fig. 3. Feedback voltage response for ML6984 and

direct acting ML7984.

Fig. 4. Feedback voltage response for reverse acting

ML7984.

Auxiliary Switch Setup

1. Drive actuator to desired position.
2. Adjust trimmer potentiometer ("trim pot") until relay

is energized. (On-board LED will light).

BRIDGE

SLOTS

1. INSTALL

CIRCUIT

BOARD

FINGERS

M32264

TRIM POT

J1

LED

+FB

NC

RLY1

-COM

C-NC CONTACT

CLOSED

WHEN VALVE

POSITION IS

BELOW TRIM POT

SETTING (DIRECT

ACTING).

C-NO CONTACT

CLOSED

WHEN VALVE

POSITION IS

ABOVE TRIM

POT SETTING

(DIRECT ACTING).

2-10 V,

(4-20 MA

INTO

500 Ω)

FEEDBACK

OUTPUT COM

CONNECT TO MAIN

BOARD FOR POSITION

FEEDBACK.

C NO

M32265

1.75V

2.5V

9.5V

10.25V

FEEDBACK VOLTAGE

LOWER

SEAT

UPPER

SEAT

STROKE

28 STEPS @

0.25V PER STEP

FIRST AND LAST STEPS

ARE @ 0.75V PER STEP

M32266

10.25V

9.5V

2.5V

1.75V

FEEDBACK VOLTAGE

LOWER

SEAT

UPPER

SEAT

STROKE

28 STEPS @

0.25V PER STEP

FIRST AND LAST STEPS

ARE @ 0.75V PER STEP

M32267