Honeywell Stryker VAV 62-2030-01 User Manual

Page 14

Advertising
background image

STRYKER VAV USER GUIDE

62-2030—01

14

RELATED TOPICS

“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

K factor

This is the VAV Box K-factor used to calculate the flow value.

IMPORTANT NOTES:

1. The K factor must be configured before starting the airflow balancing procedure.

2. The K factor must be obtained from specsheet of the terminal box manufacturer. If this is

not know, set the value to 1400.

3. Do not change the K value after the VAV box has been balanced.

4. Never set the K value to invalid or zero.

Flow Control Throttling

Range

The flow control throttling range is between 0-5000 FPM.

Flow Control Dead Band

The flow control dead band must be configured based on the damper motor speed.

For Floating actuators:

For proportional actuators:

NOTE: Proportional actuators are not recommended for pressure independent airflow

control.

NOTE: Set the Flow Control Dead Band to 30fpm when the airflow filter is enabled.

Maximum Analog Output

Change per second

The flow control maximum analog output change per second.This must be configured based on

the damper motor speed.

Minimum Analog Output

Change per Second

This is the minimum amount the Analog Output will be changed per second for flow control.

Enable Low Flow Alarm

Enable this option, if you want the controller to track and report low air flow as an alarm.

Enable airflow filter

Enable this option to filter the air flowing inside the zone.

NOTE: Note: Set the Flow Control Dead Band to 30 fpm when the airflow filter is enabled.

Table 8. Flow Setpoint Fields. (Continued)

Name

Definition

Motor Speed (sec)

Deadband (fpm)

15

125

30

65

60

30

90 to 420

20

Model Number

Deadband (fpm)

ML7174

460

ML7287

260

ML7475

330

MN7505 or MN7510 45

Motor Speed (sec)

maxAOchg per sec

15 to 90

1.1

180

0.56

420

0.24