STRYKER VAV USER GUIDE

23

62-2030—01

Two point calibration

You can start either maximum or minimum balancing in any

order. The tool does not enforce any rules on the order of

balancing.

Maximum calibration

To start maximum calibration:

Click

Start Maximum Balancing.

The device adjusts the damper to try and attain the maximum

flow setpoint. After the setpoint is attained, the Measured Flow

field is enabled and the actual measured flow value can be

entered. The device remains in manual mode (Open

Maximum) after maximum balancing is complete.

Minimum calibration

To start minimum calibration:

Click

Start Minimum Balancing.

The device adjusts the damper to try and attain the minimum

flow setpoint. After the set point is attained, the Measured

Flow field is enabled and you can enter the actual measured

flow value. The device remains in manual mode (Open

Minimum) after minimum balancing is complete.

K Factor calibration

To start K factor calibration method:

Click

Start K Factor Balancing.

After a warning message, the two point calibration data is

returned to factory defaults.

The device adjusts the damper to try and attain the maximum

flow setpoint. After the setpoint is attained, the Measured Flow

field is enabled and the actual measured flow value can be

entered.

After the measured flow is entered, the K factor value is

calculated by the tool and displayed. The tool prompts you to

write this value to the device. You can choose to calculate the

K factor without using the tool and set the calculated value in

the K factor field. The device remains in manual mode (Open

Maximum) after K factor balancing has been completed.

Heating coil water flow calibration

To override the reheat valve position:

Type the reheat value in percentage and click the Override

button next to Reheat Valve Override field.

To override the peripheral heat valve position:

Type the peripheral heat value in percentage and click the

Override button next to the Peripheral Heat Valve Override

field.

NOTE: Note: Click the Auto button to set the reheat and

peripheral heat valve into automatic operation.

Setting the device mode to automatic operation

To set the device to automatic operation:

Click

Set Mode to Auto when it is enabled.

While exiting the view if the device is in manual mode, the tool

prompts you to change the mode to automatic operation.

Restoring to factory defaults

To restore to factory defaults:

Click the

Restore to Factory Defaults button to restore the

default value of the Zero calibration values, K factor calibration

values, Minimum flow calibration values and Maximum flow

calibration values.

RELATED TOPICS

“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

15. MONITORING

Use this page to monitor the critical parameters for an Stryker VAV device on the LON network. This action can be performed with

the device in online mode. The controller must be in a commissioned state.

To monitor:

Step

Action

1

From the

Nav menu, choose Station > Driver > LON network > AscLonVAV device.

2

Right-click the device and choose

Views > Monitor from device items. The Monitor screen appears.

3

If required, you can enter the values in the editable fields.

4

Click

Write to write edited values to the controller.