3. CONFIGURING THE OUTPUTS

Use this page to configure the outputs of the Stryker VAV device as well as the parameters used to control the outputs.

To configure outputs:

Flow Type

Displays the control flow algorithm used by the controller. The selection available depends on the

Pressure Type and Box Type selected. Valid selections for this field are:

Flow Normal: The flow is controlled to satisfy the temperature control algorithm.

Flow Tracking: This VAV Terminal type consists of a single inlet air connection receiving its primary

source from the conditioned space. The outlet of the terminal is connected to a return air (or exhaust

air) system. The temperature control is turned off and the air flow is controlled to balance the flow

between several input vav boxes and one exhaust vav box in a room. This flow type is selectable

only when the Pressure Type is set to pressure independent.

Shared Wall Module: The temperature control loop is turned off and the flow is controlled by the

wall module at another master node. The NV nviShare of this controller must be bound to nvoShare

of the master node and the information received in nviShare is used to control the air flow. The

master node must have the temperature sensor connected to it and controls the space temperature

using its own damper and the other dampers of all nodes bound to it. This feature is used when only

one temperature sensor is used in a large area to control several boxes or when there is a need to

reprogram multiple satellite controllers based on flexible floor plans.

Wall Module Type

Displays the type of wall module to be used for this application. This selection determines the type of

control and options that are available from the wall module. Valid selections for this field are:

None: There is no physical wall module connection to this controller.

Conventional Wall Module: Select this when using the TR21, TR22 and TR23 series of wall

modules.

TR71/75 Wall Module: These wall modules provide access to configuration parameters and

schedule events.

Controller Power up

Disable Time

Enables you to set controller power disable time. The digital outputs of the controller are disabled for

this duration after power-up. This configuration is ignored by the controller when it is in emergency

mode.

Set Time During

Download

Enable this option to set the controller time during the download operation.

Daylight Savings

Settings

This feature enables you to select the

Daylight Savings Settings. The available options enable you

to select

Start Month, Start Day, End Month and End Day.

The tool validates the correct start and end date selection for day light savings. If the start and end

date configured is not valid then the tool displays an error and prevents the day light savings

configuration from being saved. Examples of invalid date are: February 30

th

, June 31

st

, September

31

st

.

Table 3. Stryker VAV Device Fields. (Continued)

Name

Definition

Step

Action

1

From the left pane of the

VAV Configuration Wizard, select Outputs.

2

Enter information in the available fields.

3

Click

Undo All to revert to the last saved settings.

4

Click

Next to display the Inputs page.

5

Click

Finish to save settings to station.