STRYKER VAV USER GUIDE

9

62-2030—01

Tip

When you upload the input and output values of the

configured custom sensors, you will not obtain the exact

values which you configured earlier. There will be slight loss in

precision always.

Related Topics
“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

Occupancy sensor

Operation

When an occupancy sensor is configured, this field enables you to configure the following control

operations to determine the behavior during scheduled unoccupied modes:

UnoccupiedCleaningCrew: Effective occupancy switches to standby for the comfort of the cleaning

crew.

ConferenceRoom: Effective occupancy stays unoccupied independent of the occupancy sensor

activity. During scheduled occupancy, occupancy sensor changes mode between standby and

occupied.

UnoccupiedTenant: When the occupancy sensor is active, effective occupancy switches to

occupied for the comfort of the tenant.

Custom Sensors
Sensor Name

You can configure custom sensor types when using third party sensors with the controller. You can

create a maximum of two sensor types. This page allows you to configure a 10-point sensor

characteristic curve.

NOTE: Once the sensor is configured, the same sensor name is updated in the Input

Source drop-down list. Go back to Input Source and select the Custom Sensor.

Sensor Type

Displays the sensor types such as Voltage, Resistive and Unconfigured.

Unit Measure

Displays all unit categories supported by the controller.

Specification Sheet Unit

Type

Allows you to select the unit used in the specification sheet of the sensor. This allows you to define

the sensor characters easily by referring to the specsheet.

NOTE: The controller uses a 12-bit Analog-to-Digital converter. Please ensure that the sen-

sor provides adequate resolution in the target control range. To get best perfor-

mance, make sure that the target range of sensor signals that are important for the

application can be mapped to the entire range supported by the controller with ade-

quate resolution.

Application Unit Type

This is the unit in which the sensor value will be read by the controller. To use the custom sensor for

any of the inputs expected by the controller, this unit needs to match the unit expected by the

controller.

These are the internal units used by the VAV control application:

Temperature: DegF Temperature

Setpoint: DDF or DegF

Humidity: %

CO2: ppm

Pressure: inches of water column

Import

Use this action to share/reuse custom sensor definitions. The user can import the custom sensor

definitions from other controllers or stations.

Export

Use this action to save the custom sensor in a text file.

NOTE: You must save the file with a .sen extension.

Table 5. Input Fields. (Continued)

Name

Definition