Honeywell Electronic Remote Temperature Controller T775J User Manual

Page 19

Advertising
background image

T775J ELECTRONIC REMOTE TEMPERATURE CONTROLLER

63-2248—4

19

Table 3. Checkout Table.

Checkout Table

Checkout Table Example

Heat or

Cool

Load 1

Load 2

Reset
Value

Load 1

Reset
Value

Load 2

Heat or

Cool

Load 1

Heat

Load 2

Heat

Reset
Value

Load 1

Reset
Value

Load 2

Sensor
A ____
Sensor
B ____

Sensed
Temp

Sensor A

80°

Sensor B

10°

Sensed

Temp

80° Off

76° On

80°

78° Off

74° On

120° Off
116° On

80°

118° Off

80°

Setpoint B ____________

Reset Direction __________

Setpoint B

30

°

Reset Direction

Increase

Sensor B _____________

Reset Action ____________

Sensor B

10

°

Reset Action

Below

Reset Ratio A _________

Reset Ratio B ___________

Reset Ratio A

1

Reset Ratio B

2

FORMULA 1:

FORMULA 1 EXAMPLE:

Sensor B

Sensor B = 10

°

F

-Setpoint B

Setpoint B = 30

°

F

Temp Diff = _______________________

Temp Diff =

-20

°

F

FORMULA 2:

FORMULA 2 EXAMPLE:

Amount of Reset = Reset Ratio B

Amount of Reset =

2 x (-20) = -40

Reset Ratio A

1

Advertising