Refrigeration – hussmann RGSSFP User Manual

Page 4

Advertising
background image

IGFP-RGSSFP-0008

4

INSTALLING CONDENSATE DRAIN

Poorly or improperly installed condensate drains can se-
riously interfere with the operation of this refrigerator,
and result in costly maintenance and product losses. Please
follow the recommendations listed below when installing
condensate drains to insure a proper installation:

1. Never use pipe for condensate drains smaller than

the nominal diameter of the pipe or P-trap supplied
with the case.

2. When connecting condensate drains, the P-trap

must be used as part of the condensate drain to
prevent air leakage or insect entrance. Store plumb-
ing system floor drains should be at least 14" off the
center of the case to allow use of the P-trap pipe
section. Never use two water seals in series in any
one line. Double P-traps in series will cause a lock
and prevent draining.

3. Always provide as much down hill slope (“fall”) as

possible; 1/8" per foot is the preferred minimum.
PVC pipe, when used, must be supported to main-
tain the 1/8" pitch and to prevent warping.

4. Avoid long runs of condensate drains. Long runs

make it impossible to provide the “fall” necessary for
good drainage.

REFRIGERATION LINES

LIQUID

SUCTION

3/8" O.D.

5/8" O.D.

NOTE: The standard coil is piped at 5/8" (suction); however,

the store tie-in may vary depending on the number of
coils and the draw the case has. Depending on the case
setup, the connecting point in the store may be

5

/

8

",

7

/

8

", or 1

1

/

8

". Refer to the particular case you are

hooking up.

Refrigerant lines should be sized as shown on the refrig-
eration legend furnished by the store.
Install P-traps (oil traps) at the base of all suction line ver-
tical risers.
Pressure drop can rob the system of capacity. To keep the
pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only.

CONTROL SETTINGS

See the “Case Specs” section of this guidebook for the
appropriate settings for your merchandiser. Maintain these
parameters to achieve near constant product tempera-
tures. Product temperature should be measured first thing
in the morning, after having been refrigerated overnight.
For all multiplexing, defrost should be time terminated.
Loadmaster valves are not recommended. Defrost times
should be as follows: OFF CYCLE - Three times daily for
46 minutes. The number of defrosts per day and the dura-
tion of the defrost cycle may be adjusted to meet condi-
tions present at your location.

ACCESS TO TX VALVES & DRAIN LINES

MECHANICAL - Remove the product from the bottom deck
pan. Remove pan. Remove refrigeration and drain access pan-
els (labeled). TX valve (mechanical only) and drain are lo-
cated under each access panel at end of the case.
ELECTRONIC (Remote Only) - The Electronic Expansion valve
controller is located within the electrical access panel(s).

ELECTRONIC EXPANSION VALVE (Remote Only)

A wide variety of electronic expansion valves and case
controllers can be utilized. Please refer to EEV and con-
troller manufacturers information sheet. Sensors for elec-
tronic expansion valves will be installed on the coil inlet,
coil outlet, and in the discharge air. (Some supermarkets
require a 4th sensor in the return air). Case controllers
will be located in the electrical raceway or under the case

THERMOSTATIC EXPANSION VALVE LOCATION

This device is located on the same side as the refrigera-
tion stub. A Sporlan balanced port expansion valve model
is furnished as standard equipment, unless otherwise speci-
fied by customer.

5. Provide a suitable air break between the flood rim of

the floor drain and outlet of condensate drain. 1" is
ideal.

6. Prevent condensate drains from freezing:

a. Do not install condensate drains in contact with

non-insulated suction lines. Suction lines should be
insulated with a nonabsorbent insulation material
such as Armstrong’s Armaflex.

b. Where condensate drains are located in dead air

spaces (between refrigerators or between a
refrigerator and a wall), provide means to prevent
freezing. The water seal should be insulated to
prevent condensation.

Refrigeration

REFRIGERANT TYPE

The standard refrigerant will be R-22 unless otherwise
specified on the customer order. Check the serial plate
on the case for information.

PIPING - Remote Cases Only

The refrigerant line outlets are located under the case.
Locate first the electrical box, the outlets are then on the
same side of the case but at the opposite end. Insulate
suction lines to prevent condensation drippage.

Advertising