Architectural and engineering spec, Installation of alarm, Shipping specs: technical specs – First Alert SA305B User Manual

Page 2

Advertising
background image

brkelectronics.com

ARCHITECTURAL AND ENGINEERING SPEC

TOP

VIEW

1.9”

INSTALLATION OF ALARM

The smoke alarm shall be a First Alert Model SA303

(cat no. SA303B and SA305B)

and shall provide at a minimum the following features and functions:

1. A dual ionization sensing chamber.
2. The unit shall be capable of self restoring.
3. A fully screened sensing chamber to resist entry of small insects

thereby reducing the probability of unwanted alarms.

4. Powered by a supervised 9V battery and a solid state piezo horn

rated at 85dB at 10 ft. Cat no. SA303B features a carbon zinc battery and cat no.

SA305B features a lithium battery.

5. A visual LED power-on indicator to confirm unit is receiving power or

is in alarm.

6. A full function test button. The test button should check all alarm

functions by stimulating the chamber to simulate a smoke condition,

causing the unit to alarm and also has a silence feature to silence unwanted

nuisance alarms.

7. Two Locking features - tamper resistant locking pins that lock battery drawer

and/or alarm to mounting bracket.

9. The unit shall be capable of operating between 40°F (4°C) and

100°F (38°C) and relative humidity between 10% and 90%.

10. The unit shall contain mounting hardware and shall be listed for wall

or ceiling mounting.

11. The unit shall at a minimum meet the requirements of UL217, CSFM,

NFPA 72, NFPA 101, ICC.

12. The unit shall be suitable for use in Recreational Vehicles.

Installation of this smoke alarm must conform to NFPA 72. Always check your local

building codes. Follow all instructions for placement as outlined in the user’s manual.

SHIPPING SPECS:

TECHNICAL SPECS

Individual Carton Dimensions

5.65 ”L x 2.03”W x 5.46”H

Weight

0.54 lbs.

Cube

0.036 ft3

UPC

SA303B: 0 29054 00095 8

SA305B: 0 29054 12310 7

Master Carton Dimensions

13.125”L x 5.810”W x 12.130”H

Master Pack

12

Weight

7.0 lbs.

Cube

0.535 ft3

UPC

SA303B: 100 29054 00095 5

SA305B: 100 29054 12310 4

Pallet Information

Cases per Layer

25

Number of Layers

3

Cases per Pallet

755

Units per Pallet

900

Cube

47.3 ft3

Weight

590 lbs.

Alarm Dimensions:

4.34” dia x 1.9”H

Weight:

6.8 oz.

Operating Voltage:

9V Battery Powered (SA303B carbon zinc; SA305B lithium)

Temperature Range:

40F (4C) to 100F (38C)

Humidity Range:

10% to 90% relative humidity (RH)

Audio Alarm:

85dB at 10 feet

Test/Silence:

Electronically simulates smoke condition,

causing the unit to alarm

Manual:

Press and hold test/silence button

Alarm Reset:

Automatic when smoke clears

Smoke Sensor:

Dual Ionization

Indicator Lights/Sounds:
DC Power:

Intermittent Red Light

Alarm:

Audio alarm, rapidly flashing red light

Listing:

UL to UL217 Standard

SIDE

VIEW

BACK

VIEW

CAT.

SA303B/SA305B

©2009 BRK Brands, Inc. a Jarden Corporation

Company (NYSE: JAH)

3901 Liberty Street Road

Aurora, IL 60504-8122

All rights reserved
First Alert is a registered trademark of the First Alert Trust

BRK is a registered trademark of BRK Brands, Inc.

CM2910

THE PARTS OF THIS SMOKE ALARM

BOTTOM OF ALARM

1.

Mounting bracket

2.

Mounting slots (1 of 2)

3.

Locking Pins

4.

Battery Drawer Latch

5.

Battery Drawer - Install

9V battery here

TOP OF ALARM

1.

Battery Compartment

2.

Test/Silence Button &

Red Alarm Light

BATTERY DRAWER LOCK

Remove Pin

Push locking pin through

hole near battery drawer

on the back of the alarm.

1

2

3

2

5

4

3

4.34”

Advertising