3 monitoring reference (pr. 55 , pr. 56 ), 7 restart operation parameters, 1 restart setting (pr. 57 , pr. 58 , h6 ) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 106: Restart operation parameters, Ge 96)

Advertising
background image

96

Restart operation parameters

2.6.3

Monitoring reference (Pr. 55

, Pr. 56

)

<Setting>

Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 54 "FM terminal function selection" = "0" and Pr. 56 is set when
Pr. 54 = "1".
Set the Pr. 55 and Pr. 56 values so that the output pulse train output of terminal FM is
1440 pulses/s.

2.7 Restart operation parameters

2.7.1

Restart setting (Pr. 57

, Pr. 58

, H6

)

The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).

Set the frequency
or current which
is referenced
when the output
frequency or
output current is
selected for the
terminal FM.

Parameter

Name

Factory Setting

Setting

Range

Remarks

55

Frequency monitoring
reference

60Hz

0 to 120Hz

Setting is enabled when
Pr. 30 = "1"

56

Current monitoring
reference

Rated output

current

0 to 50A

CAUTION

The maximum pulse train output of terminal FM is 2400 pulses/s. If Pr. 55 is not
adjusted, the output of terminal FM will be filled to capacity. Therefore, adjust
Pr. 55.

At power restoration after an instantaneous power failure, you can restart the
inverter without stopping the motor (with the motor coasting).

Parameter

Name

Factory

Setting

Setting

Range

Remarks

57

Restart coasting time

- - -

0 to 5s,

- - -

Setting is enabled when Pr. 30 = "1"

58

Restart cushion time

1s

0 to 60s

H6 (162)

Automatic restart after
instantaneous power
failure selection

1

0, 1, 10

Output
frequency

Pr.55

Output
frequency

Pr.56

Out

put

o

r

di

s

p

la

y

Out

put

o

r

di

s

p

la

y

1440 pulses/s (terminal FM)

1440 pulses/s (terminal FM)