MITSUBISHI ELECTRIC FR-S520E User Manual

Page 28

Advertising
background image

18

Main circuit terminals

1.2.8

Regarding noise and the installation of a noise filter

Some noise enters the inverter causing it to malfunction and others are generated by
the inverter causing the malfunction of peripheral devices. Though the inverter is
designed to be insusceptible to noise, it handles low-level signals, so it requires the
following general countermeasures to be taken.

(1) General countermeasures

• Do not run the power cables (I/O cables) and signal cables of the inverter in parallel

with each other and do not bundle them.

• Use twisted shield cables for the detector connecting and control signal cables and

connect the sheathes of the shield cables to terminal SD.

• Earth (Ground) the inverter, motor, etc. at one point.

• Capacitances exist between the inverter's I/O wiring, other cables, earth (ground)

and motor, through which leakage currents flow to cause the earth leakage circuit
breaker, earth (ground) leakage relay and external thermal relay to operate
unnecessarily. To prevent this, take appropriate measures, e.g. set the carrier
frequency in Pr. 72 to a low value, use an earth (ground) leakage circuit breaker
designed for suppression of harmonics and surges, and use the electronic thermal
relay function built in the inverter.

• The input and output of the inverter main circuit include high-degree harmonics,

which may disturb communication devices (AM radios) and sensors used near the
inverter. In this case, install a FR-BIF(-H) optional radio noise filter (for use on the
input side only) or FR-BSF01 line noise filter to minimize interference.

<Noise reduction examples>

Power
supply
for sensor

Inverter
power supply

Control
power supply

Control

box

Reduce carrier
frequency.

IM

FR-

BSF01

FR-BSF01

Sensor

Use twisted pair shielded cable.

Motor

Install filter

on inverter's output side.

Inverter

FR-BIF

Separate inverter and power
line by more than 30cm and
at least 10cm from sensor
circuit.

Install filter FR-BIF
on inverter's input side.

FR-

BSF01

FR-BSF01

Install filter

on inverter's input side.

Do not earth (ground)
control box directly.

Do not earth (ground)
control cable.

Use 4-core cable for motor
power cable and use one
cable as earth (ground) cable.

Do not earth (ground) shield but connect
it to signal common cable.

Advertising
This manual is related to the following products: