11 harmonic suppression guideline – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 31

Advertising
background image

21

Main circuit terminals

1

WI

RING

1.2.11 Harmonic suppression guideline

Harmonic currents flow from the inverter to a power receiving point via a power
transformer. The harmonic suppression guideline was established to protect other
consumers from these outgoing harmonics.
The transistorized inverter has been excluded from the target products covered by
"harmonic suppression guideline for household appliances and general-purpose
products" in January 2004. In addition, all models of transistorized inverter used by
specific consumers are covered by "harmonic suppression guideline for consumers
who receive high voltage or special high voltage" (hereinafter referred to as "guideline
for specific consumers").

"Guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a
high-voltage or specially high-voltage consumer who will install, add or renew harmonic
generating equipment. If any of the maximum values is exceeded, this guideline
requires that consumer to take certain suppression measures.

(1) Application of the guideline for specific consumers

Table 1

Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power

Received Power Voltage

5th

7th

11th

13th

17th

19th

23rd

Over

23rd

6.6 kV

3.5

2.5

1.6

1.3

1.0

0.9

0.76

0.70

22 kV

1.8

1.3

0.82

0.69

0.53

0.47

0.39

0.36

33 kV

1.2

0.86

0.55

0.46

0.35

0.32

0.26

0.24

Not more than
reference capacity

New installation/addition/
renewal of equipment

Calculation of equivalent
capacity sum

Sum of equivalent
capacities

Over reference
capacity

Calculation of outgoing
harmonic current

Is outgoing harmonic
current equal to or lower
than maximum value?

Not more than
maximum value

Harmonic suppression
technique is not required.

Over maximum value

Harmonic suppression
technique is required.

Advertising
This manual is related to the following products: