Connection to the Stand-Alone Option

1.6.3

Connection of the high power factor converter (FR-HC)

When connecting the high power factor converter (FR-HC) to suppress power supply
harmonics, perform wiring securely as shown below. Incorrect connection will damage
the high power factor converter and inverter.

CAUTION

1. Use sink logic (factory setting) when the FR-HC is connected. The FR-HC

cannot be connected when source logic is selected.

2. The power input terminals R, S, T must be open. Incorrect connection will

damage the inverter. Opposite polarity of terminals N, P will damage the
inverter.

3. The voltage phases of terminals R, S, T and terminals R4, S4, T4 must be

matched before connection.

4. Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals

used for the RES and MRS signals.

5. Do not insert NFB between terminals P-N (P - P, N - N)
6. The N terminal is not provided for the FR-S520E-0.1K to 0.75K.

From FR-HCL02

Power
supply

NFB

R

S

T

R4

S4

T4

N

P

Y1 or Y2

RDY

RSO

SE

High power factor converter (FR-HC)

Inverter

MRS (Caution 4)

RES (Caution 4)

SD

External box

FR-HCL01

R4

S4

T4

R3

S3

T3

R2

S2

T2

R

S

T

MC2
MC1

MC1 MC2

(Caution 2)

(Caution 1)

(Caution 2)

(Caution 5)

(Caution 2)

T

S

R

P

N (Caution 6)