Connection to the Stand-Alone Option

1

WI

RING

1.6.4

Connection of the power regeneration common
converter (FR-CV)

When connecting the FR-CV type power regeneration common converter, connect the
inverter terminals (P, N) and FR-CV type power regeneration common converter
terminals as shown below so that their signals match with each other.

CAUTION

1. Use sink logic (factory setting) when the FR-CV is connected. The FR-CV

cannot be connected when source logic is selected.

2. The power input terminals R, S, T must be open. Incorrect connection will

damage the inverter. Opposite polarity of terminals N, P will damage the
inverter.

3. The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1,

S2/L2, T2/L3 must be matched before connection.

4. Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals

used for the RES and MRS signals.

5. Do not insert NFB between terminals P-N (P/L+ - P, N/L

- N)

6. Make sure to connect the terminal R/L11, S/L21, T/MC1 to the power supply.

Running the inverter without connecting the terminals will damage the
power regeneration common converter.

7. The N terminal is not provided for the FR-S520E-0.1K to 0.75K.

MC

1

NFB

R/L

11

Dedicated stand-alone
reactor (FR-CVL)

S/L

21

T/L

31

R2/L

12

S2/L

22

T2/L

32

R2/L

1

S2/L

2

T2/L

3

R/L

11

S/L

21

T/MC1

P/L+

N/L-

U

V

W

IM

Three-phase
AC power
supply

FR-CV power regenerative
common converter

Inverter

PC

SD

MRS (Caution 3)

RES (Caution 3)

P24

SD

RDYB

RSO

SE

RDYA

(Caution 5)

(Caution 1)

(Caution 6)

(Caution 2)

(Caution 7)

(Caution 4)

R
S
T

P
N