Design information

1.8 Design information

1) Provide electrical and mechanical interlocks for MC1 and MC2 which are used for

commercial power supply-inverter switchover.
When the wiring is incorrect or if there is a commercial power supply-inverter
switch-over circuit as shown below, the inverter will be damaged by leakage current
from the power supply due to arcs generated at the time of switchover or chattering
caused by a sequence error.

2) If the machine must not be restarted when power is restored after a power failure,

provide a magnetic contactor in the inverter's primary circuit and also make up a
sequence which will not switch on the start signal.
If the start signal (start switch) remains on after a power failure, the inverter will
automatically restart as soon as the power is restored.

3) Since the input signals to the control circuit are on a low level, use two or more

parallel micro signal contacts or a twin contact for contact inputs to prevent a
contact fault.

4) Do not apply a large voltage to the contact input terminals (e.g. STF) of the control

circuit.

5) Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp

etc.

6) Make sure that the specifications and rating match the system requirements.

1) Commercial power supply-inverter

switchover

3) Low-level signal contacts

Power

supply

Inverter

Leakage current

Interlock

MC2

MC1

U

V

W

IM

R

S
T

Low-level signal contacts

Twin contact