Polarity of the power supply terminals 5-1 – MITSUBISHI ELECTRIC MITSUBISHI MAM MAM-AM24 User Manual

Page 24

Advertising
background image

Setting the operating mode on the DIP switch

NOTE

RS485 stipulates that the cables should be terminated at both ends of the transmission sec-
tion. The termination prevents signal reflections in the cables and in times of no data trans-
mission, enforces a defined idle state on the bus. This termination can be implemented
using, for example, specific resistors at the screw terminal. It can also be implemented via
the DIP switches on the Mitsubishi Alarm Modem.

RS422 Connection

RS485 2-wire connection (2-wire bus system, half-duplex)

In this operating mode, transmit cables and receive cables are interconnected. If the Mitsubishi
Alarm Modem is installed at the beginning (first station) or end (last station) of the bus system,
the bus system must be terminated by setting the DIP switches accordingly.

RS485 / RS422

Interfaces

4 - 4

MITSUBISHI ELECTRIC

COM2

Device B

T–

T–

T+

T+

(0

V)

R–

R–

R+

R+

Fig. 4-7:
The receiving lines are to be connected to
R+ (other end T+) and
R- (other end T-),
the sending lines to
T+ (other end R+) and
T- (other end R-)
according to the opposite sketch.

Operating mode

DIP 1

DIP 2

DIP 3

DIP 4

DIP

Two-wire RS485 with termination

1

1

1

1

1111

Two-wire RS485 without termination

0

0

1

1

0011

Four-wire RS485 without termination

0

0

0

0

0000

Four-wire RS485 with termination of receive cable

1

1

0

0

1100

RS422

0

0

0

0

0000

Tab. 4-1:

Setting the operating mode on the DIP switch

Bus Master

COM2

Slave 1

(0

V)

R–/T–

R+/T+

Slave 2

R–/T–

R+/T+

Slave 3

R–

T–

R+

T+

T–

R–

T+

R+

Fig. 4-8:
The twisted pair cable is to be connected to
T+ to T+ or R+ and for
T- to T- or R-
according to the opposite sketch.