3 explanation of functions (parameters), 1 torque boost [p 0] [p46, 1 torque boost – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 67

Advertising
background image

58

2

.3 Explanation of Functions (Parameters)

2

.3.1

Torque boost

Increase this value for use when the
inverter-to-motor distance is long or
motor torque is insufficient in the low
speed range (stall prevention is
activated).

Motor torque in the low-frequency

range can be adjusted to the load
to increase the starting motor
torque.

Pr.0
Pr.46

Setting range

0 Output frequency (Hz)

Out

p

u

t

vo

lt

a

g

e

Parameter

Name

Factory

Setting

Setting

Range

Remarks

0

Torque boost

6%/5%/4%

(Note)

0 to 15%

(Note) FR-S520 (S)-0.1K to 3.7K: 6%

FR-S540-0.4K, 0.75K: 6%
FR-S510W-0.1K to 0.75K: 6%
FR-S540-1.5K, 2.2K: 5%
FR-S540-3.7K: 4%

46

Second torque boost

- - -

0 to 15%,

- - -

- - -: Function invalid. Setting is
enabled when Pr. 30 = "1".

<Setting>

Assuming that the base frequency voltage is 100%, set the 0Hz voltage in %.
Use the RT signal to switch between two different torque boosts. (Turn on the RT
signal to make Pr. 46 valid(*).)

REMARKS

* The RT signal acts as the second function selection signal and makes the other

second functions valid.

When using an inverter-dedicated motor (constant-torque motor), make setting as

indicated below.

•

FR-S520-0.1K to 0.75K ..... 6%, FR-S520-1.5K to 3.7K ..... 4%

•

FR-S540-0.4K, 0.75K ..... 6%, FR-S540-1.5K ..... 4%,

FR-S540-2.2K, 3.7K ..... 3%

•

FR-S520S-0.1K to 0.75K ..... 6%, FR-S520S-1.5K ..... 4%

•

FR-S510W-0.1K to 0.75K ..... 6%

If you leave the factory setting as it is and change the Pr. 71 value to the setting for
use of the constant-torque motor, the Pr. 0 setting changes to the above value.

CAUTION

•

Selecting automatic torque boost control makes this parameter setting invalid.

•

A too large setting may cause the motor to overheat or result in an overcurrent
trip. The guideline is about 10% at the greatest.

♦

♦

♦

♦

Related parameters

♦

♦

♦

♦

RT signal (second function "Pr. 46") setting

⇒

Pr. 60 to Pr. 63 "input terminal function

selection" (refer to page 88)

Constant-torque motor setting

⇒

Pr. 71 "applied motor" (refer to page 93)

Automatic torque boost control selection

⇒

Pr. 98 "automatic torque boost selection (motor

capacity)" (refer to page 109)