S

ensor styles

Fig. 4

Style 1a (drawn bulb)

Fig.5

Style 1b swaged bulb, can be used with

closed-tank connector FTG13A-600

½" x 14 NPT

33.3

60

Fig. 6

Style 4h

½" x 14 NPT

58.3

60

Fig. 7

Style 2

Fig. 8

Style 20

Fig. 9

Style 3 (coil)

B

ulb size and finish, bulb wells

Range (°C)

Style

Bulb size

(mm)

Finish

Bulb well (optional)

-35 to +10

1b

9.5 x 110

Tin-plated

WEL14A602R

-35 to +10

3

-

Stainless Steel

-

-5 to +28

1b

9.5 x 135

Tin-plated

WEL14A603R

-5 to +28

3

-

Stainless Steel

-

-35 to +40

1b

9.5 x 110

Tin-plated

WEL14A602R

-35 to +40

3

-

Stainless Steel

-

0 to 13

1a

9.3 x 80

-

WEL16A601R

0 to 43

3

-

Stainless Steel

-

1 to 60

1b

9.5 x 115

-

WEL14A602R

5 to 32

1b

9.5 x 155

Tin-plated

No bulb well available

10 to 95

1a

7.4 x 75

-

WEL11A601R

40 to 120

1b

9.5 x 100

-

WEL14A602R

35 to 150

1a

5 x 265

-

No bulb well or closed tank

connector possible

90 to 290

1a

5 x 155

-

No bulb well or closed tank

connector possible