Type number selection – Johnson Controls Thermostat A19A User Manual

Page 4

Advertising
background image

A19A

Issue 03/03/2003

Catalogue Section 1

© 2003 Johnson Controls Inc.

Order No. PD-A19A-E

4

T

ype number selection table:

Range
( °C)

Diff.
(K)

Bulb

style

Setting

(see page 2

adjustment)

Cap.

length

Max.
bulb
temp.

Wholesaler
code

Order
number

Type A19AAC Capillary thermostat, fixed differential

-35 to +10

2.5

1b

set low

2 m

60 °C

A19AAC-9102

-5 to +28

2

1b

set low

2 m

60 °C

A19AAC-9005

-5 to +28

2

1b

set low

5 m

60 °C

A19AAC-9124

1 to 60

2

1b

set low

3 m

85 °C

A19AAC-9127

40 to 120

3.5

1b

set high

2 m

145 °C

A19AAC-9009

35 to 150

4

1a

set high

2 m

180 °C

A19AAC-9107

90 to 290

5.5

1a

set high

2 m

290 °C

A19AAC-9108

Type A19ABC Capillary or immersion thermostat, adjustable differential

-35 to +40

2.8 to 8

1b

set low

3.5 m

60 °C

A19-A4

A19ABC-9037

-35 to +40

2.8 to 8

1b

set low

6.5 m

60 °C

A19-A5

A19ABC-9036

-35 to +10

2.8 to 11

1b

set low

2 m

60 °C

A19-A1

A19ABC-9103

-5 to +28

2 to 8

1b

set low

2 m

60 °C

A19-A2

A19ABC-9104

1 to 60

2 to 8

1b

set low

5 m

85 °C

A19ABC-9117

1 to 60

2 to 8

1b

set low

3 m

85 °C

A19-A3

A19ABC-9116

10 to 95

3.5 to 13 1a

set high

3.5 m

115 °C

A19ABC-9106

40 to 120

3.5 to 13 2

set high

-

145 °C

A19ABC-9011
bulb well incl.

40 to 120

3.5 to 13 4h

set high

2 m

145 °C

A19ABC-9012
bulb well incl.

Type A19ACC Capillary thermostat, lock-out low with manual reset

-35 to +10

6

M

1b

set low

2 m

60 °C

A19ACC-9100

-35 to +10 N

6

M

1b

set low

3.5 m

60 °C

A19ACC-9105

-35 to +10 N

6

M

1b

set low

5 m

60 °C

A19ACC-9111

-35 to +10 N

6

M

1b

set low

6.5 m

60 °C

A19-F

A19ACC-9116

-5 to +28

4

M

1b

set low

2 m

60 °C

A19ACC-9101

-5 to +28

4

M

1b

set low

5 m

60 °C

A19ACC-9103

-5 to +28

4

M

1b

set low

3 m

60 °C

A19ACC-9107

Type A19ADC immersion thermostat, lock-out high with manual reset

40 to 120

7

O

2

set high

-

145 °C

A19ADC-9200

bulb well incl.

Type A19AAF Capillary thermostat, close, fixed differential

0 to 10

1.5

1a

set low

2 m

80 °C

A19AAF-9101

0 to 10

1.5

1a

set low

2 m

80 °C

A19-M P

A19AAF-9102

5 to 32

0.75

1b

set high

2 m

60 °C

A19AAF-9103

M

Indicates temperature increase above cut-out

point to make reset possible.

N

Low limit stop factory set +2.5 °C may be

removed in the field.

O

Indicates temperature decrease below cut-

out point to make reset possible.

P

Milk-cooler thermostat.

Advertising
This manual is related to the following products: