Specifications, Pecifications – Johnson Controls Thermostat A19A User Manual

Page 8

Advertising
background image

A19A

Issue 9811

Catalogue Section 1

© 2003 Johnson Controls Inc.

Order No. PD-A19A-E

8

S

pecifications

CE Conformity According to low voltage directive and EMC directive

Operating range -35 to +290 °C. See type number selection table.

Differential See type number selection table.

Differential adjustments Controls with adjustable differential (types A19ABC and A19BBC) have

an adjustment lever under the cover.

Sensor styles Styles 1a, 1b, 2, 3, 4h, and 20 (see drawings page 3)

Electrical ratings ~15(8) A, 230 V; except A19AAF and A19DAF: ~15(3) A 230 V, and

A19ABC-9036/9037: ~15(5) A 230 V

Ambient temp. limits -35 to +55 °C

Conduit opening 22.3 mm diam. hole for PG-16 connector

Material Case

1.75 mm cold-rolled zinc plated steel

Cover

1.5 mm ABS plastic

Protection Class IP30

Shipping weight

Individual pack 0.4 kg
Overpack

10 kg (24 pcs)

Dimensions (see dimension drawing)

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond
these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.

Johnson Controls International, Inc.

Headquarters:

Milwaukee, WI, USA

European Headquarters:

Westendhof 8, 45143 Essen, Germany

European Factories:

Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany)

Branch Offices:

Principal European Cities.

This document is subject to change

Printed in Europe

Advertising
This manual is related to the following products: