Electric heat, Thermostat, Power and control wiring – Johnson Controls SUNLINE 2000 BQ 060 User Manual

Page 10: Options/accessories, Control wire sizes

Advertising
background image

364985-XIM-B-0508

10

Johnson Controls Unitary Products

THERMOSTAT

The room thermostat should be located on an inside
wall approximately 56 inches above the floor where it
will not be subject to drafts, sun exposure or heat from
electrical fixtures or appliances. Follow the manufac-
turer's instructions enclosed with the thermostat for
general installation procedure. A minimum of seven
color-coded insulated wires (#18 AWG) should be used
to connect the thermostat to the unit.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of
the National Electrical Code, ANSI / NFPA No. 70 (in
U.S.A.), current Canadian Electrical Code C22.1 (in
Canada) and/or local ordinances. The unit must be
electrically grounded in accordance with NEC and CEC
(as specified above) and/or local codes. Voltage toler-
ances, which must be maintained at the compressor
terminals, during starting and running conditions, are
indicated on the unit Rating Plate and the Unit Applica-
tion Data table.

The internal wiring harness furnished with this unit is
an integral part of a CSA design certified unit. Field
alteration to comply with electrical codes should not be
required.

A fused disconnect switch should be field provided for
the unit. The switch must be separate from all other cir-
cuits. Wire entry at knockout openings require conduit
fittings to comply with NEC (in U.S.A.), CEC (in Can-
ada) and/or local codes. If any of the wire supplied with
the unit must be replaced, replacement wire must be of
the type shown on the wiring diagram and the same
minimum gauge as the replaced wire.

Use copper conductors properly sized to carry the load.
Each unit must be wired with a separate branch circuit
fed directly from the meter panel and properly fused.

Refer to the Typical Field Wiring Figure 3 and to the
appropriate unit wiring diagram for control circuit and
power wiring information.

OPTIONS/ACCESSORIES

ELECTRIC HEAT

The factory- or field-installed heaters are wired for sin-
gle point power supply. Power supply need only be
brought into the single point terminal block and thermo-
stat wiring to the low voltage terminal strip located in
the upper portion of the unit control box.

These CSA approved heaters are located within the
central compartment of the unit with the heater ele-
ments extending into the supply air chamber. Refer to
Figure 7 for access panel location.

Fuses are supplied, where required, by the factory.
Some KW sizes require fuses and others do not. Refer
to Table 3 for minimum CFM limitations and to Tables
9 through 14 for electrical data.

When connecting electrical power and control
wiring to the unit, waterproof type connectors
MUST BE USED so that water or moisture
cannot be drawn into the unit during normal
operation. The above waterproofing conditions
will also apply when installing a field-supplied
disconnect switch.

TABLE 2: CONTROL WIRE SIZES

Wire Size

Maximum Length

1

1. From the unit to the thermostat and back to the unit.

18 AWG

150 Feet

Advertising
This manual is related to the following products: