8.5 Error status register

The HR 60 and HR 61 error status registers (holding register - 16-bit) are used to indicate con-
troller or system errors. HR 60 contains general alarms, whereas special faults are entered in
HR 61. In modem mode (Co9 -> Fb01 = ON), the change in state of HR 60 or HR 61 causes the
controller to dial the control system.

In InF8 level the bits of the error status register are displayed:

4

FSR1 (general error):
The corresponding block at the top is set for every bit set

4

FSR2 (special error):
by pressing

key, the set bits are displayed similar to FSr1

In both cases, the blocks 20 to 23 are visible when a bit is set in another error status register
(which is currently not visible) to make it immediately recognizable whether one of the maxi-
mum 32 error flags has been set.

Holding register 60

(A set bit is indicated by

on the right of number):

Number = Bit no. in HR

0 1 2 3 4 5 6 7 8 9 10 11

Bit value

2

0

2

1

2

2

2

3

2

4

2

5

2

6

2

7

2

8

2

9

2

10

2

11

Sensor breakage

D0

Default values read

D1

–

D2

Mode switch RK1 faulty

D3

Mode switch RK2 faulty

D4

Mode switch RK3 faulty

D5

Unauthorized access

D6

Error alarm of a BE

D7

WMZ error alarm issued to
meter bus

D8

WMZ error alarm issued

D9

–

D10

Fault alarm binary output
changed

D11

72

EB 5179 EN

Operational faults