3. Maintenance
57
031-132-B0-001 Rev. A
TM
©2000
3.15 Replacing Cabinet Exhaust Duct Upper Seal
1. Remove old seal and clean duct
edge with rubbing alcohol, or
other non-acid-based cleaning
solution.
2. Peel backing from sealing strip and
apply to surface of duct.
3. Verify sealing material covers
the open corners of the duct
4. Trim excess sealing material and
replace enclosure.
End of Procedure
NOTE:
The enclosure must be removed to gain access to the
exhaust duct upper seal. Contact Alpha Technologies
Technical Support at 1-800-863-3364 for information
regarding this procedure.
Allow 15 minutes for completion of procedure
Tools required:
Rubbing Alcohol or similar non-acid-based cleaner
Scissors
Removal and replacement procedure: