15 ecm - apu control interface, Interconnection – Alpha Technologies AlphaGen 5.0kW Auxiliary Power Unit User Manual
Page 81

4. Interconnection
81
031-132-B0-001 Rev. A
TM
©2000
4.3
Connectors, continued
Pin Description
Function
1
+12V Ignition Battery
Ignition battery Fused 12V from APU
2
Neg Ignition Battery
Ignition Battery Negative from APU
3
Low Oil Pressure
Active LOW signal denotes Low Oil Pressure.
4
Over-Temp
Active LOW signal indicates Over-Temp.
5
Start Command
Active LOW from ECM activates APU START
relay.
6
Common (Start Stop)
Common return between Start and Stop relays.
7
Stop Command
Active LOW from ECM activates APU STOP
relay.
8
Over-Speed
Active LOW signal denotes engine RPM was
exceeded.
9
Over-Crank
Active LOW signal denotes Over Crank Limit is
reached.
10
Engine Run
Active LOW signal denotes the Engine is
running.
11
Not Used
12
Not Used
4.3.15 ECM - APU Control Interface
The interface control is a 12-pin (2x6 row) Mini Mate-N-Lok style connector.
See Fig. 4-9, item 12 for location.