Gas Heating















Gas piping must be installed in accordance
with local codes, or in the absence of local
codes, installation must conform to the
current (United States) National Fuel Gas
Code ANSI-Z223.1/NFPA 54 or the current

(Canada)

National

Fuel

&

Propane

Installation Code CSA B149.1 or B149.2.

Table 3 - Gas Piping Connections

Model

Option

B2

Quantity of

Heat

Exchangers

Connections

Quantity

Size

1, 2, 3,

or 4

8 or less

1

2”

5 or 6

10 or 12

1

3”


Do not use gas piping smaller than unit gas
connections. Natural gas pipe runs longer
than 20 feet may require a larger supply pipe
than the unit connection size. Some utility
companies may also require pipe sizes larger
than the minimum sizes listed.

See unit nameplate for unit gas heating
capacities or the Unit Rating Sheet, which
can be obtained from the AAON sales
representative.

Table 4 - Natural Gas Maximum Piping Capacities (ft

3

/hr)

- Specific Gravity = 0.6, Supply Pressure ≤ 0.5 psi, Pressure Drop = 0.5” w.c.

Pipe Size

Length of Pipe

20 ft

50 ft.

100 ft.

150 ft.

200 ft.

2”

2785

1696

1165

936

801

2-1/2”

4437

2703

1857

1492

1277

3”

7843

4778

3284

2637

2257

3-1/2”

11484

6995

4808

3861

3304

4”

15998

9745

6698

5378

4603


Piping Sizing Example
A 100 ft pipe run is needed for a 1710 MBH
natural gas heater. The natural gas has a
rating of 1000 BTU/ft

3

and a specific gravity

of 0.6 (Obtain these values from the local
gas supplier.)

BTU

ft

MBH

1000

1710

3

1710 ft

3

/hr

From the natural gas maximum capacities
table, at 100 ft and 1710 ft

3

/hr the required

minimum pipe size is 2-1/2”.

Inlet and Manifold Pressures
For natural gas units, the minimum inlet gas
pressure to the unit is 6” w.c. and maximum
inlet gas pressure to the unit is 10.5” w.c.
For propane units, the minimum inlet gas
pressure to the unit is 11” w.c. and the
maximum inlet gas pressure to the unit is
13” w.c. A field provided 1/8” NPT pressure
tap is required to be installed in the piping
just upstream of the shutoff valve for test
gage connection to allow checking of the
gas supply pressure at the unit.


FOR YOUR SAFETY

Read

the

entire

gas

heating

installation section of this manual
before beginning installation of the
gas heating section.

If you do not follow these instructions
exactly, a fire or explosion may result
causing property damage, personal
injury or loss of life.