Troubleshooting guide, Fault possible cause fix – LiftMaster J door operator User Manual

Page 38

Advertising
background image

38

TROUBLESHOOTING

TROUBLESHOOTING GUIDE

THE OPERATOR WILL
NOT RESPOND TO ANY
COMMANDS

POWER LED IS NOT ON

STOP BUTTON LED IS
NOT ON

THE DOOR WILL MOVE
ABOUT A FOOT THEN
STOP. AFTER STOPPING,
ONLY CONSTANT
PRESSURE COMMANDS
WILL MOVE THE DOOR

THE DOOR WILL MOVE
MOST OF THE WAY
TOWARDS A LIMIT THEN
STOP. AN EXTRA OPEN OR
CLOSE COMMAND IS ABLE
TO GET DOOR TO
COMPLETE CYCLE

THE DOOR WILL OPEN
SOME BUT NOT
COMPLETELY. AN EXTRA
OPEN IS ABLE TO GET THE
DOOR TO OPEN
COMPLETELY

THE DOOR WILL OPEN BUT
WILL ONLY CLOSE AFTER
A FIVE SECOND DELAY
WITH CONSTANT
PRESSURE ON THE CLOSE
BUTTON (RESTRICTED
CLOSE MODE)

a) No power supply

Verify primary line voltage from power source. Green POWER LED

must be on.

b) Operator control station is wired wrong

Use the OPEN, CLOSE and STOP LEDs to help check correct wiring.

Verify that the board is accepting commands by using the onboard

station. Green LED next to stop button must be on.

c) Interlock switch is activated

Check Interlock(s). If more than one external interlock is present they

must be wired in series. Green LED next to stop button must be on.

d) Dial still in programming, option,

Set dial to desired wiring type.

or diagnostic mode
e) Motor is malfunctioning

Verify proper voltage getting to the motor (Check motor name plate).

f) Motor thermal overload tripped

Check to see if motor is hot. Allow motor to cool before attempting to

move door. Cycle operator in constant pressure one full cycle open and
close to reset fault.

g) Possible accessory malfunction

Disconnect all devices, reattach them one at a time testing for a failure

after each one is replaced.

h) Off Board relay may need to be

When the OPEN or CLOSE button is pressed, Relay A or B LED should

replaced see wiring diagram

turn on and the door should move in the corresponding direction. If

Relay A or B lights and the door does not move, off board relay may

need to be replaced (see wiring diagram Off Board Relays).

i) Possible logic board failure

Replace logic board.

a) Control station not connected or wired

Check wiring to control station.

correctly
b) Interlock switch

Check interlock switch(es) for continuity.

a) The photoelectric sensors, edge or

If the on board LMEP LED is flashing, the photoelectric sensor are

other sensing device is obstructed

misaligned or not connected. Remove any obstructions, check the

or activated

safety device wires for continuity and shorts.

b) The logic board thinks that the direct

Unlearn the photoelectric sensors from the memory by resetting

connect photoelectric sensors are

factory defaults.

attached and blocked

FAULT

POSSIBLE CAUSE

FIX

a) RPM sensor is not connected properly

Check the RPM assembly for loose connections. Check that RPM wheel

or may need to be replaced

is turning when operator is running. Check for foreign matter blocking

optical lens.

Replace RPM sensor.

b) Clutch slipping

Adjust clutch and verify that door is not binding.

The Maximum Run Timer is not set

Manually reprogram the Maximum Run Timer (page 35).

correctly

OR reset the factory defaults (page 35).

There may be a Mid Stop set

Check to see if the Mid Stop LED is on. Clear the Mid Stop by turning

the selector dial to program. Press and hold the MID STOP button for
5 seconds. Return dial to desired wiring type.
To reset Open Mid Stop refer to page 33.

a) Loose secondary wiring connections

Repair or replace connections or control transformer.

or a faulty control transformer
b) Hoist interlock switch

Check interlock. Verify the manual release chain is not engaged.

Troubleshooting guide

Advertising