Part Names and Functions

Name

Description

A

Upper Rotary
DIP switch

Define the CANopen node ID (1 to 127). When using GP as a
master, available range of node ID is 1 to 63. Do not use the same
node ID twice in the network.

• Left Rotary DIP switch :

Sets tens place with 0 to12 (decimal number)

• Right Rotary DIP switch :

Sets ones place with 0 to 9 (decimal number)

B

Lower Rotary
DIP switch

Define the baud rate. Set the baud rate with 0 to 9 (decimal
number). Set the baud rates identical to those on the master unit
(such as the GP unit).

Front

Right side

A

B

C

F

H

E

D

G

* The Interface (1) on the Left side of HTB is unable to use.

Position (lower encoder rate)

Baud Rate

0

10 kbits/s

1

20 kbits/s

2

50 kbits/s

3

125 kbits/s

4

250 kbits/s

5

500 kbits/s

6

800 kbits/s

7

1 Mbits/s

8

Automatic

9

Default rate (250 kbits/s)

Note: GP3000 Series CANopen board type is corresponding

to the baud rate between 50 kbits/s and 1 Mbits/s.

Note: The value 8 is used to search automatically for the bus

transmission speed. The search starts at a value of 1
Mbits/s then progressively lowers over successive
searches until communication is established on the bus.
The automatic search only works on an operational
CANopen network.