2 master settings, 3 integration of gsd, Master settings -2 – Yokogawa EJA115 User Manual

Page 17: Integration of gsd -2

Advertising
background image

IM 01C22T03-00E

4-2

4. GETTING STARTED

4.2 Master Settings

To activate PROFIBUS PA, the following bus
parameters must be set for the master.

Table 4.2 Bus Parameters

The maximum time a master
station must wait for the
complete reception of the
first octet of a response (11
bits).
e.g: 4095

Sets the minimum time at
which a slave can send the
first bit of a response back.

Sets the maximum time at
which a slave can send the
first bit of a response back.

Controls the time at which
the bus electronics or
software of the sender is set
to receive mode after a
message is sent.

Sets the maximum allowable
time for parameter setting
and response by the slave.

Sets the number of token
cycles after which the
master will search for a new
master.

Sets the number of retries
that are performed after a
receiver does not respond to
a message.

Sets the highest station
address in the network.

The transmission rate of
PROFIBUS PA matches that
of the segment coupler.
e.g P+F: 93.75 kbps,
Siemens: 45.45 kbps

Description and Settings

Transmission
rate

T

SL

min T

SDR

max T

SDR

T

SET

G

max. retry
limit

HSA

T

QUI

Transmission
Rate

Slot Time

Min. Station
Delay Timer

Max. Station
Delay Time

Setup Time

Gap update
factor

Max Retry
Limit

Highest Station
Address

Quiet Time

Symbol

Parameter

T0402.EPS

4.3 Integration of GSD

A PROFIBUS PA system requires a GSD file
containing device parameters such as the supported
transmission rate, input data, output data, data format
and data length.
The following GSD files are available for the EJA.

Table 4.3 GSD files

PA139701.GSD (AIx2)

0x9701

Profile GSD file

0x070D

Device Specific Ident-Number

YEC_070D.GSD

Device Specific GSD file

Profile Ident-Number

T0403.EPS