7. IN-PROCESS OPERATION

7.2.2 Status of Each Parameter in Failure

Mode

The DTM and EDDL messages when the LCD
indicates an alarm are listed in the following table.

Table 7.1 Status of each parameter in failure mode

Alarm

Display

Cause of Alarm

Transducer Block

AI1/AI2 Block

AL. 01

Capsule Module Failure

Pressure/Measured value. Quality
=BAD-Sensor Failure

Static Pressure/sensor Temperature.
Quality=BAD-Sensor Failure

Output Value and Quality depend on
Fail Safe Mode *1

AL. 02

AMP Module Failure 1

AMP Module Failure 3

Pressure/Measured value.Quality
=BAD- Device Failure

Static Pressure/sensor Temperature.
Quality=BAD- Device Failure

Output Value and Quality depend on
Fail Safe Mode *1

AL. 03

AMP Module Failure 2

Pressure/Measured value. Quality
=BAD-Device Failure

Static Pressure/sensor Temperature.
Quality=BAD- Device Failure

Output Value and Quality depend on
Fail Safe Mode *1

AL. 21

Physical Block is in
O/S mode

Pressure/Measured value. Quality
=BAD

Static Pressure/sensor Temperature.
Quality=BAD

Output Quality=Bad-Out of Service

AL. 22

Transducer Block is in
O/S mode

Pressure/Measured value. Quality
=BAD-Out of Service

Static Pressure/sensor Temperature.
Quality=BAD-Out of Service

Output Quality=Bad-Out of Service

AL. 42

Static Pressure is out
Of normal range

Pressure/Measured value. Quality
= Uncertain

Static Pressure. Quality
= Uncertain-value uncertain
Sensor Temperature. Quality
= Uncertain

Output Quality=
Uncertain

AL. 43

Fluid temperature is
out of normal range

Pressure/Measured value. Quality
= Uncertain

Static Pressure. Quality
= Uncertain
Sensor Temperature. Quality
= Uncertain-value uncertain

Output Quality=
Uncertain

AL. 41

Differential Pressure is
out of normal range

Pressure/Measured value. Quality=
Uncertain- value uncertain

Static Pressure/sensor Temperature.
Quality= Uncertain

Output Quality=Uncertain
value uncertain

AL. 23

AI1 Block is in O/S mode

AI1 Output Quality=Bad-Out of Service

AL. 61

Data is out of LCD
Display range

AL. 62

Simulation is enabled
in AI1 Block

AI1 Output Value and Quality are
Simulated

AL. 63

AI Block is in MAN mode

AI1 Output Value and Quality are
user set value

AL. 64

Zero adjust value is out
Of normal range

Pressure/Measured value. Quality
=BAD: Configuration error

Output Value and Quality depend on
Fail Safe Mode *1

AI2 Block is in O/S mode

AI2 Output Quality
=Bad- Out of Service

T0701.EPS