7. IN-PROCESS OPERATION

*1: Table 7.2 Fail Safe Mode

Value

Status (Quality)

Value

Status (Quality)

Value

Status (Quality)

Output Value and Status (Quality)

Fail Safe Default
Value

UNCERTAIN
Substitute Value

Last stored valid
OUT value

UNCERTAIN Last
Usable Value

wrong calculated
value

BAD_*(* as
calculated)

0

Default value is
used as output
value

1

Storing last valid
Output value

2

The calculated
output value is
incorrect

No.

Fail Safe Mode

T0702.EPS

7.3 Simulation

The simulation function simulates the input of the AI
block and lets it operate as if the data were received
from the transducer block.

When the simulation parameter is set to “enable”, the
applicable AI block uses the simulation value set in
this parameter instead of the data from the transducer
block.

Table 7.3 Simulation parameter

Simulation

Control the simulation function of
this block
Disabled(standard) or
Enabled(simulation)

Simulation Value

Sets the value of the data to be
simulated.

Simulation Quality
and Status

Sets the data status(quality) to be
simulated

Parameters

Description

T0703.EPS

In simulation enabled status, an alarm (AL.62) is
generated from the physical block, and other device
alarms will be masked; for this reason the simulation
must be disabled immediately after using this function.

NOTE

Fail safe mode function has a priority over
simulation function. In this case, value and
status setting by fail safe mode output.

The Setting procedure is as follows;

Example: Simulation Quality: Good, Status: OK,

Output Value: 50 (%)
( Scale In: 0 to 100kPa, Out Scale: 0 to
100kPa)

From the DTM-Works window, click [Device]

[Connect]

Click [Device]

[Parameter]

[Online]

Double-click on [Output] folder

Click on [Analog

Input 1] folder

Change Simulation to [Enabled]

Change Simulation Value to [50] (%)

Change Simulation Quality to [Good]

Change Status to [OK]

The output value is displayed in the Output Value
field.

Change Simulation to [Disabled].

Figure 7.2 Simulation