9. GENERAL SPECIFICATIONS

9.

GENERAL SPECIFICATIONS

9.1 Standard Specifications

For items other than those described below, refer to
the corresponding General Specification sheet.

Applicable Model:

EJA110A, 120A, 130A, 210A, 220A,
EJA310A, 430A, 440A, 510A, 530A,
EJA115, 118W, 118N, 118Y, 438W, 438N

Output Signal:

Digital communication signal based on PROFIBUS-PA
protocol.

Supply Voltage:

9 to 32 V DC for general use, flameproof type, and
nonincendive.

9 to 24 V DC for intrinsically safe type Entity model
9 to 17.5 V DC for intrinsically safe type FISCO model

Conditions of Communication Line:

Supply Voltage: 9 to 32 V DC
Current Draw: 16.5 mA (max)

Power Supply Effect:

No effect (within the supply voltage of 9 to 32 V DC)

External Zero Adjustment:

External zero is continuously adjustable with 0.01%
incremental resolution of maximum span.

Functional Specifications:

Functional specifications for PROFIBUS communica-
tion conform to the PROFIBUS-PA ver 3.0.
Function Block: Two AI blocks

EMC Conformity Standards:

,

EN61326, AS/NZS CISPR11

<Settings When Shipped>

T0901.EPS

Tag Number(TAG )

‘PT1001’ unless otherwise specified in order.

(Not engraved on tag plate in such case.)

*1

Output Mode (Characterization Type)

‘Linear’ unless otherwise specified in order.

Calibration Range (Scale In Lower/Upper Value)

As specified in order

Unit (Pressure Unit) of Calibration Range

Selected from mmH

2

O, inH

2

O, ftH

2

O, mmHg, inHg, Pa, hpa, kPa,

MPa, g/cm

2

, kg/cm

2

,

bar, mbar, psi, torr, atm (Only one unit can

be specified.)

Output Scale (Out Scale Lower/Upper Value)

‘0 to 100%’ unless otherwise specified in order.

Unit of Output Scale (Out Scale : Unit)

As specified in order

Damping Time Constant (Filter Time Const)

‘2 sec’

Bus Address

‘0x7E(126)’ unless otherwise specified in order.

*1: Specified Tag Number is entered in the amplifier memory and also engraved on the stainless steel plate.

- For entry in the amplifier memory: Up to 32 letters using any of alphanumereics and symbols, - and ·

- For engraving on the stainless steel plate: Up to
16 letters using any of alphanumereics and
symbols, -, ·, and /.

< Related Instruments >

The customer should prepare instrument maintenance

tool, terminator, and Profibus power supply etc.

< DP/PA Coupler for CENELEC (KEMA) Intrinsically

Safe Type >

Supplier

DP transmission Rate

Model

45.45kbps

6ES7 157-0AD82-0XA0

T0902.EPS

SIEMENS

97.75kbps

KFD2-BR-Ex1.3 PA.93

P+F