2. Connection

2.1 Integral Indicator Display

When Powering On

For models with the integral indicator code “D”, the

display shows all segments in the LCD and then

changes to the displays shown below sequentially.

All segments display

Model name (3 s)

Communication Protocol (3 s)

Device Revision (3 s)

F0200.ai

Either “5” or “7” is displayed on the “Communication

Protocol” display as HART protocol revision

followed by device revision number on the “Device

Revision” display.

NOTE

This function is available for software revision

2.02 or later.

Software revision can be checked by the

following procedure.

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu](Refer to subsection

3.1.1) → Review → Software rev

EJX_HART 5[1.2]

DTM

Configuration → Device

information1 → Software rev

NOTE

In this User’s Manual, HART protocol revision

5 and 7 are described as HART 5 and HART 7

respectively.

NOTE

LCD display can be set to “All segments display”

only.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7

/EJA:HART 5)

[Root Menu] (Refer to subsection

3.1.1) → Detailed setup → Display

condition → Chg power on info

DTM

(EJX:HART 5)

Configuration → Local Display

→ Chg power on info

ON

Show all segments display, Model

name, Communication Protocol, and

Device Revision when powering on.

OFF

Show all segments display when

powering on.

2.2 HART Protocol Revision

For the models with the output signal code “-J”,

HART protocol revision 5 or 7 is selectable. The

protocol revision is set as specified in the order.
The typical function which is available by HART

protocol revision 7 is listed as follows. Refer to

HART 7 description in this document or

HART 7

mark

for detail.

• Long Tag Supporting Up to 32 Characters

Long tag secures a better asset management

with abundant digits in its software.

• Enhanced Burst Mode and Event Notification

Advanced burst mode includes the variety

of transmission setting by specifying burst

variables, update period, and message trigger

mode, and event notification function gives

you alert signal based on the status change in

preset values and self-diagnosis.

• Squawk

Identifying the transmitter by displaying the

particular pattern on LCD

• Multidrop Communication

Up to 63 transmitters can be connected. An

analog signal output available for one device in

a loop.

How to confirm protocol revision is shown below.
There are three ways to confirm the protocol

revision set to the transmitter.