6 power supply voltage and load resistance, Power supply voltage and load resistance -4 – Yokogawa EJX115A User Manual

Page 13

Advertising
background image

<2. Connection>

2-4

IM 01C25T01-06EN

2.5 Interconnection Between

DPharp and the HART

Configuration Tool

The HART configuration tool can interface with the

transmitter from the control room, the transmitter

site, or any other wiring termination point in the

loop, provided there is a minimum of 250 Ω

between the connection and the power supply. To

communicate, it must be connected in parallel with

the transmitter; the connections are non-polarized.

Figure 2.2 illustrates the wiring connections for

direct interface at the transmitter site for the

DPharp. The HART configuration tool can be used

for remote access from any terminal strip as well.

USB

FieldMate

Modem

Relaying

terminals

Distributor

Control room

Terminal

board

F0202.ai

USB

PC/FieldMate

HART configuration tool

DPharp

SUPPL

Y

PULSE

CHECK

ALARM

Figure 2.2

Connecting the HART Configuration

Tool

2.6 Power Supply Voltage and

Load Resistance

When configuring the loop, make sure that the

external load resistance is within the range in the

figure below.

(Note) With an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.

600

250

0

10.5 16.6

25.2

42

External

load

resistance

R (Ω)

Power supply voltage E (V DC)

F0203.ai

Communication

applicable range

R= E–10.5

0.0244

Figure 2.3

Relationship between Power Supply

Voltage and External Load Resistance