6 output signal low cut mode setup, 7 impulse line connection orientation setup, Output signal low cut mode setup -14 – Yokogawa EJX115A User Manual

Page 27: Impulse line connection orientation setup -14

Advertising
background image

<3. Parameter Setting>

3-14

IM 01C25T01-06EN

• Procedure to call up the

Quick resp display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup →

Signal condition → Quick resp →

EJX_HART 5[1.2]

DTM

Configuration → Analog Output →

Quick resp →

→ Off

Set from 0.50 to 100.00

→ On

Set from 0.00 to 100.00

3.2.6 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output

signal near the zero point.
The low cut point can be set in a range from 0 to

20%, the direct ratio corresponding to the output

signal of 4 to 20 mA. (Hysteresis for the cut point:

±10% of the cut point)
Either “Linear” or “Zero” can be selected as the low

cut mode. Unless otherwise specified, the cut mode

is set to “Linear” at the factory.
The default value of Low cut is set according to the

combination of the Output mode (Xfer fnctn) and

Integral indicator display mode (Disp Pres % fnctn).

See below table.

Relationship of default value of Low cut and

Low cut point

Combination of

output mode and

display mode

Default

value of

Low cut

Low cut

point for

the output

signal/

display

# Output

mode

Display

mode

1) Linear

Linear

10%

10% / 10%

2) Sq Root Sq Root

10%

10% / 10%

3) Linear Sq Root

1%*

1% / 10%

4) Sq Root Linear

10%

10% / NA

*: It is applied for software revision 2.02 or later. For

previous software version, it is set in 10%.

In the case 3) above, Low cut point for the display is

square root of Low cut value.

(Example: Low cut value; 2%, Low cut point; 14%)

Note that when the output modes of the output

signal and the display are selected as “Sq root”

and “Linear” accordingly, the low cut function is not

available for the display value.

(%)

50

(%)

50

0

50

(%)

50

(%)

Output

Output

For low cut in linear mode

Input

20

20

0

For low cut in zero mode

Input

F0302.ai

Example: Low cut at 20%

Figure 3.1

Low Cut Mode

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

EJX_HART 5[1.2]

DTM

Easy Setup → or Configuration →

Analog Output →

→ Low cut

Set from 0 to 20% of output

→ Low cut mode

Select “Linear” or “Zero”

The low cut point has hysteresis so that the output

around the point is behaved as below figure.
<Example>

Output mode: Linear

Low cut mode: Zero

Low cut: 20.00%

F0303.ai

Setting range: 0 to 20%

2% 2%

4mA

Output

Low cut point

Input

Hysteresis

fixed at 10%

of the cut point

7.2mA

(20%)

3.2.7 Impulse Line Connection Orientation

Setup

This function reverses the impulse line orientation.
Follow the procedure below to assign the high

pressure impulse line connection to the L side of the

transmitter.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Basic setup →

EJX_HART 5[1.2]

DTM

Configuration → Pressure Sensor

→ H/L Swap

Select “Normal” or “Reverse”