2 analog output signal adjustable range, 3 integral indicator display mode, 4 integral indicator scale setup – Yokogawa EJX115A User Manual

Page 29: Analog output signal adjustable range -16, Integral indicator display mode -16, Integral indicator scale setup -16

Advertising
background image

<3. Parameter Setting>

3-16

IM 01C25T01-06EN

3.3.2 Analog Output Signal Adjustable

Range

Output signal adjustable range at normal operating

condition are set as shown below at the factory

when the instrument is shipped, and output signal

are limited by these value.

Lower limit

Upper limit

Standard

Option code /C1

3.6 mA

21.6 mA

Option code /C2 and /C3

3.8 mA

20.5 mA

Output signal range can be changed between

3.6mA and 21.6mA to match it to the equipment on

the receiving side.

Lower value is set at

AO lower limit and upper

value is set at

AO upper limit respectively.

Follow the procedure below to change the upper

and lower values.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup →

Output condition → Analog output

EJX_HART 5[1.2]

DTM

Configuration → Analog output →

→ AO lower limit

Set the lower value (mA)

→ AO upper limit

Set the upper value (mA)

Set the values as below.

Lower value < Upper value

3.3.3 Integral Indicator Display Mode

The mode setting for the output signal and the

integral indicator can be performed independently.
The output mode for the integral indicator is set

as specified in the order when the instrument is

shipped. Follow the procedure below to change the

mode.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→ Display condition → P disp

condition →

EJX_HART 5[1.2]

DTM

Configuration → Local Display

→ Disp Pres % fnctn Select “Linear” or “Sq root”

If the instrument is equipped with an integral

indicator and the transfer function is sq root, “

” is

displayed on the integral indicator.

3.3.4 Integral Indicator Scale Setup

The following five displays are available for integral

indicators: input pressure, % of range, user set

scale, input static pressure*

1

, and % of static

pressure range*

1

. A cycle of up to four displays can

be shown by assigning variables to the parameters

at

Disp select.

F0305.ai

Available displays

Input pressure

(PRES)

% of range

(PRES %)

User set scale

(ENGR. PRES)

Input static pressure

(SP)*

1

% of static pressure range

(SP %)*

1

Indicates values of input pressure

with the indication limits –99999 to

99999.

Indicates input pressure in –2.5 to

110% range depending on the

set range (

LRV and URV).

Indicates values depending on the

engineering range (

Engr LRV and

Engr URV) with the unit (Engr Unit).

Indicates input static pressure with

the indication limits –99999 to 99999.

Reference pressure is factory-set in

absolute.

Indicates input static pressure in

–10 to 110% range depending on

the set range (

SP LRV and SP

URV).

PRES

456 kPa

Description

and related parameters

PRES % 45.6 %

SP

4.000 MPa

SP %

52.6 %

Engr LRV 0.0

Engr URV 45.0

Engr exp ×100

Engr Unit m3/min

Engr point 1

*1: Available for differential pressure transmitter.

See (a.) through (d.) shown below for the setting

procedures.