10 software write protection, Software write protection -21 – Yokogawa EJX115A User Manual

Page 34

Advertising
background image

<3. Parameter Setting>

3-21

IM 01C25T01-06EN

3.3.9 CPU Failure Burnout Direction and

Hardware Write Protect

There are two slide switches on the CPU assembly

board. One sets the burnout direction at CPU

failure, and the other sets a write protection function

which disables parameter changes through

the use of a handheld terminal or some other

communication method.

HIGH

LOW

CPU assembly

Slide switch

Burnout direction switch

Write protection switch

Write Protection

Switch Position

Burnout Direction

Switch Position

BO H

L

WR E

D

H

L

E

D

H

L

E

D

H

L

H

L

Hardware write protection switch (WR)

Burnout direction switch (BO)

Burnout Direction

Write Protection

YES

(Write disabled)

NO

(Write enabled)

F0307.ai

The parameter of

AO alm typ parameter displays

the status of 4-20 mA DC output if a CPU failure

occurs. In case of a failure, communication is

disabled.
Standard specifications or with option code /C3

The burnout direction switch is set to “HIGH”. If a

failure occurs, the transmitter outputs a 110% or

higher signal.
With option code /C1 or /C2

The burnout direction switch is set to “LOW”. If a

failure occurs, a –5% or lower output is generated.
To confirm the burnout direction at the CPU failure,

follow the procedure below.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→Output condition → Analog

output → AO alm typ

EJX_HART 5[1.2]

DTM

Configuration → Analog output →

AO alm typ

High

Burnout direction is set to High

Low

Burnout direction is set to Low

3.3.10 Software Write Protection

The transmitter configured data is saved by using a

write protection function. The write protection status

is set to “Yes” when 8 alphanumeric characters are

entered in the

New password field and transferred

to the transmitter.
When write protection is set to ”Yes,” the transmitter

does not accept parameter changes. When the

same eight alphanumeric string entered in the

New

password field is also entered in the Enable wrt

10min field and transferred to the transmitter, it

will be possible to change transmitter parameters

during a 10 minute period.
To change the transmitter from the write protection

”Yes” status back to write protection ”No” status,

use

Enable wrt 10min to first release the write

protection function and then enter eight spaces in

the

New password field.

• Procedure to call up the display using by DD

and DTM (excluding EJX HART 5 DTM based

on FDT1.2)

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→ Device information → Field

device info → Wrt protect menu

→ Write protect

Display current protect mode

(Yes: protected, No: not

protected)

→ Enable wrt 10

min

Release the protect function for

10 min.

→ New password

Set the new password or change

the password

• Procedure to call up the display by EJX HART 5

DTM based on FDT1.2

EJX HART 5

DTM based on

FDT1.2

Write Protect →

→ Write Protect Display current protect mode

(Yes: protected, No: not protected)

→ Enter new

password

Enter the password here to enable

the protect function.

Enter eight spaces to disable the

protect function.

→ Enable write Enter the password here to release

the protect function for 10 min.

Advertising