<3. Parameter Setting>

3-23

IM 01C25T01-06EN

(2) Threshold Level Setting
Set the threshold of high and low alert value for

alarm generation.

• Procedure to call up the display by DD and

DTM (EJX HART 5 DTM based on FDT1.2)

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed

setup→ Output condition →

Process Alerts → Pres Alert

(DTM only) → Config Pres

Alerts →

→ Hi Alert Val

Set the threshold value of upper

side for pressure

→ Lo Alert Val

Set the threshold value of lower

side for pressure

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed

setup→ Output condition →

Process Alerts → SP Alert (DTM

only) → Config SP Alerts →

→ SP Hi Alert Val

Set the threshold value of upper

side for static pressure

→ SP Lo Alert Val

Set the threshold value of lower

side for static pressure

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed

setup→ Output condition →

Process Alerts → Temp Alert

(DTM only) → Config Temp

Alerts →

→ Temp Hi Alert Val Set the threshold value of upper

side for capsule temperature

→ Temp Lo Alert Val Set the threshold value of lower

side for capsule temperature

• Procedure to call up the display by EJX HART 5

DTM based on FDT1.2

EJX HART 5 DTM

based on FDT1.2

Configuration → Process Alerts

→ Hi Alert Val

Set the threshold value of upper

side for pressure

→ Lo Alert Val

Set the threshold value of lower

side for pressure

→ SP Hi Alert Val

Set the threshold value of upper

side for static pressure

→ SP Lo Alert Val

Set the threshold value of lower

side for static pressure

→ Temp Hi Alert Val Set the threshold value of upper

side for capsule temperature

→ Temp Lo Alert Val Set the threshold value of lower

side for capsule temperature

NOTE

When option code /DG6 is specified,

Diag can

be also assigned to Status. The Hi Alert Val or

Lo Alert Val for

Diag is defined by the following

parameters.

[Impulse Line Blockage Detection]

Limit meters to detect the blockage and

Condition error for ILBD operation is defined.

Refer to 4.2.2.1.
[Heat Trace Monitoring]

Flg temp Hi Alert Val and Flg temp Lo Alert

Val parameters are used as the upper and

lower threshold for Status output. Refer to

4.2.3.2.

3.3.13 Status Output (only for EJX series:

option code AL)

EJX

The transmitter has a contact output.

Select the type of output, status output, and set the

unit, value etc.
(1) Setting of status output
This feature is used for a transistor output (open

collector) of an on/off signal according to the

status of high and low alarm limits, which are

user-configurable values as shown in subsection

3.3.12 Alarm. The status output can be assigned

as any combination of the high or low limits of the

input pressure, input static pressure, or capsule

temperature.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→Output condition → Process

Alerts → DO config → DO Select

EJX_HART 5

[1.2] DTM

Configuration → Process Alerts →

DO Select

Display Item

Contents (Select a output variable

from the list below)

Off

Pres

Differential pressure

SP

Static pressure

Temp

Temperature

Pres/SP

Pressure and static pressure

Pres/Temp

Pressure and temperature

SP/Temp

Static pressure and temperature

Pres/SP/Temp

Pressure, static pressure and

temperature

Diag Alarm

Alarm for advanced diagnostics

(Refer to subsection 4.2.2.5)

All

Alarm for pressure, static pressure,

temperature, and advanced

diagnostics