<3. Parameter Setting>

3-25

IM 01C25T01-06EN

Transmitter

L

h

0

H

(+)

● EJX118A/EJA118E

F0310.ai

h

h

L

L

H

Transmitter

Transmitter

0

(+)

(–)

● EJX438A/EJA438E

Note: When the transmitter is positioned lower than the

diaphragm seal part, the value of “h” must have a

negative sign (–).

Example: Enter K value obtained from the equation (a).

A value haivng up to 3 decimal places may be

specified.

When h=+3 m, Fill fluid code A, span=15 kPa,

K=−(+3)Ч0.00745ч15Ч100=−0.149

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→ Signal condition → T.Z.

Comp menu →

EJX_HART 5[1.2]

DTM

Configuration → Pressure

Sensor →

→ Temp Zero

Set the compensation value

Input “-0.149” to

Temp Zero prameter.

Note 1: The function is performed using a built-in temperature

sensor in the transmitter body. The temperature

deviation between the transmitter body and capillaries

should be minimized to achieve optimal performance

of the function.

Note 2: When the span changes, reenter the newly obtained

value of K to

Temp Zero.

Table A. Constant value [B] of fill fluid

Fill fluid

code

A, C,

1, 2, 4

B

D

E

C

on

st

an

t v

al

ue

[B

]

mmH

2

O

0.76

0.87

1.45

0.75

kgf/cm

2

0.000076 0.000087 0.000145 0.000075

kPa

0.00745

0.00853

0.01422

0.00736

mBar

0.07453

0.08532

0.14220

0.07355

atm

0.000074 0.000084 0.000140 0.000073

inH

2

O

0.02992

0.03425

0.05709

0.02953

psi

0.00108

0.00124

0.00206

0.00167

mmHg

0.05592

0.06401

0.10669

0.05518

Note 3: Select the unit of constant value of [B] from the actual

unit used for the transmitter in operation.

3.3.15 Test Output, Simulation, and Squawk

NOTE

Fixed current output, DO Test, and Device

Variable Simulation Function continue for a given

holding time, then is released automatically.

Even if the HART configuration tool power

supply is turned off or the communication cable

is disconnected, the test output will continue for

that time.

The holding time can be selected from 10 min*,

30 min, 60 min, 3 hour, 6 hour or 12 hour.

*: Default value.
• Procedure to call up the display

DD

[Root Menu] → Diag/Service →

Test Auto Release Time

DTM (excluding

EJX_HART 5

[1.2])

[Root Menu] → Diag/Service →

Test → Test Auto Release Time

EJX_HART 5[1.2]

DTM

Diag and Service → Service

→ Test Auto Release Time

(1) Fixed current output
This feature can be used to output a fixed current

for loop checks. The available range for test output

depend on the settings for the

AO lower limit and

AO upper limit parameters, whose limit is from

3.6mA (-2.5%) to 21.6mA (110%).

Refer to the subsection 3.3.2 about the setting of

AO lower limit and AO upper limit.

While this function works, “TEST” is displayed on

the integral indicator.

Setting by DD and DTM (EJX HART 5 DTM

based on FDT1.2)

Call up the test output parameter (Loop test) and

select the output signal.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service →

Test (DTM only) → Loop test →

Display Item

Contents

4mA

Output a 4mA DC signal

20mA

Output a 20mA DC signal

Other

Set a desired output signal value

End

Exit