16 burst mode, 1 in the case of using hart 5, 2 in the case of using hart 7 – Yokogawa EJX115A User Manual

Page 40

Advertising
background image

<3. Parameter Setting>

3-27

IM 01C25T01-06EN

• Procedure to call up the

Squawk display

[Root Menu] → Diag/Service → Test (DTM)/Test device

(DD) → Squawk

P

S P

T

F

F0311.ai

Figure 3.3

LCD display for Squawk

3.3.16 Burst Mode

3.3.16.1 In the case of using HART 5

HART 5

When the

Burst mode is enabled, the transmitter

continuously sends the stored data. The data is

sent approximately three times per second as a

digital signal when the transmitter is set in burst

mode. When data is being sent in burst mode,

other operations can be performed with the HART

configuration tool.

(1) Selection of the transmission data.
Call up the

Burst option parameter and select the

data which is transferred.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup →

Output condition → HART output

→ Burst option →

EJX_HART 5[1.2]

DTM

Configuration → HART → Burst

option →

Display Item

Contents

PV

Process variable assigned to PV

(Either of pressure, static pressure)

%range/current

Output in % and mA

Process vars/crnt Output in mA and process variables

assigned to PV, SV and TV.

(Output in mA, pressure, static

pressure and capsule temperature)

(2) Shift to the Burst mode.
To enable the Burst mode, select “On” at the

Burst

mode parameter.

To release the

Burst mode, call up the Burst

mode display and set it to “Off”.

This parameter is set to “Off” when the instrument is

shipped.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup →

Output condition → HART output

→ Burst mode

EJX_HART 5[1.2]

DTM

Configuration → HART → Burst

mode

Display Item

Contents

Off

Stop the burst mode

On

Start the burst mode

3.3.16.2 In the case of using HART 7

HART 7

When the

Burst mode is enabled, the transmitter

continuously sends up to three data listed in Table

3.1.

Refer to the subsection 3.3.16.2.1 Burst Message

for details.

When the

Burst mode is set to “Wired HART

Enabled”, transmitter continuously sends alarm

signal also.

Refer to subsection 3.3.16.2.2 Event Notification for

detail.

When changing the setting of

Burst mode, set “Off”

to the

Burst mode.

Default setting is “Off”.

3.3.16.2.1 Burst Message and Burst Mode

(1) Burst message
The transmitter can transmit three burst messages

at the maximum.

The parameters for

Burst Message are as follows.

• Burst Command

• Update Period and Max Update Period

• Burst Msg Trigger Mode

Advertising