2 setting on hart 7, 18 switching hart protocol revision, 2 setting on hart 7 -33 – Yokogawa EJX115A User Manual

Page 46: Switching hart protocol revision -33, Important

Advertising
background image

<3. Parameter Setting>

3-33

IM 01C25T01-06EN

3.3.17.2 Setting on HART 7

HART 7

“Multidropping” transmitters refer to the connection

of several transmitters to a single communication

transmission line. Up to 63 transmitters can be

connected when set in the multidrop mode. To

activate multidrop communication, the transmitter

address must be changed to a number from 1 to 63.

If it sets to multidrop mode, in order to transmit all

the data in digital one, it is necessary to change a

setup of the analog output signal of 4 to 20 mA.

Setting of Multidrop Mode

(1) Polling address

• Procedure to call up the display

DD and DTM

[Root Menu] → Detailed setup

→Output condition →HART

output →

→ Poll addr

Enter the number from 1 to 63

NOTE

When the same polling address is set for

two or more transmitters in multidrop mode,

communication with these transmitters is

disabled.

(2) Analog Output Signal Setting
Set Disabled to

Loop current mode and fix

an analog output signal to 4mADC. It becomes

impossible in this case, to also use a burnout

output.
However, in the case of the application which

receives and operates an analog output signal, an

analog output signal can be used for one loop. In

this case, set Enabled to

Loop current mode.

• Procedure to call up the display

DD and DTM

[Root Menu] → Detailed setup

→Output condition →Analog output

→ Loop current mode →

Enabled

Loop current mode is enabled.

Disabled

Loop current mode is disabled.

(3) Enabling the Multidrop Mode of

Configuration Tool

About the procedure to call up the

Polling

display, please refer to the User’s Manual of each

configuration tool.

(4) Communication when set in multidrop

mode.

• The HART configuration tool searches for a

transmitter that is set in multidrop mode when

it is turned on. When the HART configuration

tool is connected to the transmitter, the polling

address and the tag will be displayed.

• Select the desired transmitter. After that, normal

communication to the selected transmitter is

possible. However, the communication speed

will be slow.

To release multidrop mode, call up the

Poll addr

display and set the address to “0”.
Return

Loop current mode to Enabled.

3.3.18 Switching HART Protocol Revision

When the output signal code is “-J”, HART protocol

revision of the transmitter can be selectable from 5

or 7.

The HART protocol revision is set and shipped as

specified in the order.

To change the HART protocol revision after

shipment, follow the procedure shown below.

IMPORTANT

When changing the protocol revision, confirm the

items below.

• Protocol revision supported by HART

configuration tool must be the same or

higher than new protocol revision of the

transmitter. (Refer to Table 2.1)

• Confirm that the DD or DTM which is suitable

to new protocol revision of transmitter is

installed in the configuration tool. (Refer to

Section 2.3 or 2.4)

1) Call up the parameter for protocol revision

change

• Procedure to call up the

Chg universal rev

display.

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Detailed setup

→ Device information → Field

device info → Revision #’s → Chg

universal rev

EJX_HART 5[1.2]

DTM

Configuration → HART → Chg

universal rev