3 operation parameters, 3 operation parameters -9, 3 operation parameters  diag mode – Yokogawa EJX115A User Manual

Page 56

Advertising
background image

<4. Diagnostics>

4-9

IM 01C25T01-06EN

Ref fDP:

OK

Ref fSPI:

OK

Ref fSPh:

OK

Ref BlkF:

OK

Fluctuation Parameters

• Test for low-pressure side

• Test for high-pressure side

• Test for both-pressure sides

Simulation Test

• B Blocking detection

(by using

Ratio fDP)

• L Side Blocking detection

(by using

Ratio fSPI)

• H Side Blocking detection

(by using

Ratio fSPh)

• H/L Side Blocking detection

(by using

BlkF)

Ref fDP:

OK

Ref fSPI:

OK

Ref fSPh:

OK

Ref BlkF:

NG

• Test for low-pressure side

• Test for high-pressure side

• Test for both-pressure sides

• A/B Blocking detection

(by using

Ratio fDP)

• L Side Blocking detection

(by using

Ratio fSPl)

• H Side Blocking detection

(by using

Ratio fSPh)

Ref fDP:

OK

Ref fSPI:

NG

Ref fSPh:

OK

Ref BlkF:

NG

• Test for high-pressure side

• A Blocking detection

(by using

Ratio fDP)

• H Side Blocking detection

(by using

Ratio fSPh)

Ref fDP:

OK

Ref fSPI:

NG

Ref fSPh:

NG

Ref BlkF:

NG

• Test for both-pressure sides

• B Blocking detection

(by using

Ratio fDP)

Available Blockage Detection

[Differential pressure measurement]

[Gauge/absolute pressure and level measurement]

Ref fDP:

OK

Fluctuation Parameters

Simulation Test

• Test for high-pressure side

• B Blocking detection

(by using

Ratio fDP)

Available Blockage Detection

F0405.ai

4.2.2.3 Operation Parameters

Diag Mode

Diag Mode gives the directive for the ILBD

operation. There are following three modes.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service

→ Diag Parameters → ILBD

Parameters → Configuration → Set

Diag Mode →

EJX_HART 5[1.2]

DTM

Diag and Service → Advanced Diag

Configurations → Impulse Line

Blockage Detection → Diag Mode

Diag Mode

Mode

Function

Stop

The blockage detection operation is

stopped.

Calculation The blockage detection operation is

performed.

Alarms are generated along with the

result.

Reference Reference values for the blockage

detection are obtained and updated to the

latest. After sampling reference values,

this mode changes to "Calculation".

When the blockage detection operation is

performed, set “Calculation” to

Diag Mode. “Stop”

must be set when you change a threshold value or

set an alarm. “Reference” is set in order to obtain

the reference fluctuation values under the normal

configuration.