<4. Diagnostics>

4-22

IM 01C25T01-06EN

Amplifier

Temperature

Capsule

Temperature

Amp temp

Snsr temp

Flg Temp Coef

Flg temp

Execution HTM

CT+(CT-AT) x Cf

Calculation of

Flg temp

Snsr temp

Flg temp

Diag Error

Display on LCD

Response Code

(Device Status)

Status group 9

Contact Output

(Digital Output)

4-20mA DC

(Analog Output)

Amp temp

Sensor signals

Sensor

Process Value

calculation

Alarm Masking

Result of HTM detection

HTM alarm

Result of HTM detection

DO Config

HTM alarm

HTM alarm

Diag Output

Option

F0412.ai

Figure 4.9

Functional Block Diagram of Heat Trace Monitoring (HTM)

4.2.3.2 Out of Temperature Measurement

Range

When the flange temperature is out of

measurement range, the alarm or alert is

generated. For the detail of alarm and alert setting,

refer to subsection 4.2.2.5.
The measurement range is set to

Flg Temp Hi

Alert Val and Flg Temp Lo Alert Val, which values

can be specified within -50 to 130 deg C.

Flgtemp

Flg temp

F0413.ai

Time

Time

An alarm is generated.

An alarm is generated.

Flg Temp Hi Alert

Flg Temp Lo Alert