Parameter summary, Parameter summary -1 – Yokogawa EJX115A User Manual

Page 79

Advertising
background image

<5. Parameter Summary>

5-1

IM 01C25T01-06EN

5. Parameter Summary

Function

Label

Item

Contents

Default value Handling

*

1

Analog output AO alm typ

Analog output alarm type

High or Low

R

AO lower limit

Lower limit of analog output

3.6000 to 21.6000 mA

3.6000 mA

W

AO upper limit

Upper limit of analog output

3.6000 to 21.6000 mA

21.6000 mA

W

Auto recover

Auto-recover from hardware error

Off or On

On

W

Analog output

trim

Clear D/A trim

Reset analog output trim

M

D/A trim

Analog output trim with ammeter

M

Scaled D/A trim

Analog output trim with voltmeter

M

Channel flags

Analog channel flags

0x00

R

Bi-directional

mode

Bi-dir mode

Bi-directional mode

Off or On

Off

W

Burst mode

Burst mode

Burst mode *

2

Off or On

HART 5

Off or Wired HART Enabled

HART 7

Off

W

Burst option

HART 5

Burst option

Xmtr Variables, PV, % range/

current, Process vars/crnt

W

Burst Command

HART 7

Burst Command *

2

Cmd 1: PV

Cmd 2: % range/current

Cmd 3: Dyn vars/current

Cmd 9: Device vars w/status

Cmd 48: Read Additional

Device Status.

Cmd 1: PV

W

Burst Variable

Code (DD)

Device Variable

Code (DTM)

HART 7

Device Variable for the Burst

Message *

2

Max 8 slots.

W

Burst Msg Trigger

Mode

HART 7

Burst Trigger Mode Selection Code

*

2

(Continuous, Window, Rising,

Falling, On-change)

Continuous

R

Set Burst Trigger

HART 7

Configure burst trigger

Configure Burst Msg Trigger

Mode and Burst Trigger Level

M

Set Burst Period

HART 7

Configure burst period

Configure Update Period and

Max Update Period

M

Burst Trigger Level

HART 7

Burst Trigger Level *

2

0.0

R

Update Period

HART 7

Update Period for Burst mode *

2

Update period for burst

message

Burst Message

1: 0.5s

2: 60s

3: 60s

R

Max Update Period

HART 7

Max Update Period for Burst mode

*

2

Maximum update period for

burst message

60 min

R

Damping

Pres Damp

Damping time constant for DP

0.00 to 100.00 s

W

Quick resp

Quick response

On or Off

Off

W

Date

Date

Date

**/**/**

W

Descriptor

Descriptor

Descriptor

16 alphanumerics

W

*1:

Handling:

R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,

D=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.

*2:

Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

*3:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.