Operation, Operation 5.1 hart, Networks – KROHNE OPTITEMP TT 50 C-R EN User Manual
Page 21
OPERATION
5
21
OPTITEMP TT 50 C/R
www.krohne.com
09/2010 - 4000636502 - MA OPTITEMP TT 50 C/R R03 en
Operation
5.1 HART
®
networks
5.1.1 Point-to-point connection analog / digital mode
Point-to-point connection between the transmitter and the HART
®
master.
The current output of the device may be active or passive.
DANGER!
Only connect an Ex approved HART
®
modem located in a safe area to a transmitter in a
potentially explosive area.
CAUTION!
In order to ensure reliable HART
®
communication with this transmitter, the loop resistance
must be at least 250 Ω!
1 Primary Master
2 HART
®
modem
3 HART
®
signal
4 Analog indicator
5 Terminal 5
6 Terminal 6
7 Device with address = 0 and passive or active current output
8 Secondary Master
9 Power supply for devices (slaves) with passive current output
10 Load ≥ 250 Ω (Ohm)