Operation, 2 factory settings for configuration – KROHNE OPTITEMP TT 50 C-R EN User Manual
Page 23
OPERATION
5
23
OPTITEMP TT 50 C/R
www.krohne.com
09/2010 - 4000636502 - MA OPTITEMP TT 50 C/R R03 en
5.2 Factory settings for configuration
The transmitter are delivered with either a factory settings or configured according to
customers' specifications.
DANGER!
Only connect an Ex approved HART
®
modem located in a safe area to a transmitter in a
potentially explosive area.
Menu
Parameter
Factory settings
Device Root
menu
-> Sensor
Type of sensor 1
RTD Pt100 α=0.003850
Number of wires
3
PV Lower range value
0
PV Upper range value
100
Digital units
°
C
Lock code
Unlocked
Isolation resistance monitoring
Off
Sensor break (Off/Down scale/Up scale)
Up scale
Sensor short circuit (Off/Down scale/Up scale)
Off
Span
0...+100°C / +32...+212°F