Setting power capping – HP ProLiant DL170e G6 Server User Manual

Page 42

Advertising
background image

Power capping 42

The following text is an example output when an advanced license was not installed on four chassis (1 1, 1

6, 1 7, and 1 10).

> set power baseline

Before running a baseline calibration - ensure that

your configuration has all machines turned on and are

running processes that are typical of the type of workload

you expect them to run in a production environment.

This process will briefly impact the performance of the

servers that are being baseline calibrated as well as

temporarily speed up the fans.

Are you sure you wish to set a new power baseline for this system? (Y/N/Q)

-> Yes

Retrieving license information for chassis Power Manager port 1, Dist. Module

port 1

Verifying..done

One or more servers located in chassis at Power Manager port 1, Dist. Module

port 1 is not licensed for the power capping feature.

This chassis will be skipped for baselining purposes.

Note: All licensed servers should be booted up at least once

so the BIOS/ROM can write the relevant license information

to the chassis controller.

Retrieving license information for chassis Power Manager port 1, Dist. Module

port 2

Verifying..done

Setting power capping

Use the SET POWER CAP command to specify a power cap. The command takes an AC wattage range that

must be between the minimum and maximum values that were set with the SET POWER BASELINE command

and are shown with the SHOW POWER BASELINE command.
In this example, APM Port (item 1) and DM Port (item 2) are illustrated.

> show power baseline
APMPort DMPort Serial Number Min Cap Max Cap Set Cap Slots Populated

------- ------ ------------- ------- ------- ------- ----- ----------------

1 2 CNK71600K4 585 2372 1500 (8) 2 3 5 7

------- ------- -------

585 2372 1500

Advertising