Figure 12 DC Terminals, Ribbon Cables, and Auxiliary Terminals

WARNING: Shock Hazard and Equipment Damage

It may be necessary to remove the ribbon cables in the course of servicing the Radian. (This is detailed in

the Radian service manual.) The cables must never be removed until all power has been disconnected from
the Radian for a minimum of one minute. If the cables are removed prematurely, the Radian’s capacitors

will retain a sizable charge, which can cause electrical shock or severe equipment damage during normal

handling. This damage is not covered under the unit’s warranty.

12V AUX: Delivers 12 Vdc up to

0.7 amps (8.4 watts). The output can
be switched on and off for many
functions. See page 25 for details.

SWITCH INV eceives wires for a

manual on/off switch to control the
inverter. See page 24 for instructions.

NOTE: The ON/OFF INV jumper (J3)

overrides these terminals when installed.
(See above.)

RELAY AUX: Relay contacts with no

voltage (10 amps at 250 Vac or 30 Vdc).
The relay can be switched on and off for
many functions. See page 25 for details.

ON/OFF INV JUMPER (J3): Overrides the

SWITCH INV terminals when installed. When
installed, the inverter is ON. The ON or OFF states

can then only be controlled by the system display.

NOTE: J3 is installed to the ON position during
manufacture, but the Radian inverter is given an

external OFF command at the same time.

Its initial state will be OFF.

DC TERMINALS Connects to the battery cables and DC system. There are
two DC positive and two DC negative terminals. Each DC positive terminal

requires separate cables and separate overcurrent protection. See page 20

for instructions.

RIBBON CABLES Connects the Radian’s power
modules and control board. See Warning below.

The functions for each set of AUX contacts can be programmed